BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Electrical Applications  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M382731
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 54 MULBERRY STREET MANHATTAN BIN: 1001810     Block: 164   Lot: 13
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 54 MULBERRY ST Census Tract:   29 Health Area:  7700
1/F Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   103
DOB Cross Street(s):   MOSCO STREET,    BAYARD STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/10/2016 1:37 PM
Application Entered:   06/10/2016 Job Start Date:   06/15/2016
Last Change:   08/22/2025 Job End Date:   06/15/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     08/22/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 012124 Licensee Name: AI FANG WU
Firm: 003828 Firm Name: KWONG MING ELECTRIC INC
Firm Phone: 718-266-2883  Firm Address: 2516 MCDONALD AVENUE BROOKLYN NY 11223 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $77.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RITA LAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    12  11    12             
Buildings Total 12  11    12                
Total Units : 41 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 08/23/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  EXISTING A/C.

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M382731
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/22/2016 08/23/2016 BUR V (35) (8)
INSPECTION COMMENTS: DESERT STORE, FEEDER AND GENERAL WIRING

OBJECTION FOR APPLICATION #: M382731
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(CELLAR) NO FIREPROOFING PROVIDED FEEDER CABLE PASSING THROUGH FLOOR
OPEN 08/22/2016 08/22/2016
 
002 (999) OTHER
(CELLAR) OLD FEEDER NOT SUFFICIENT FOR NEW LOAD LOAD
OPEN 08/22/2016 08/22/2016
 
003 (999) OTHER
(CELLAR) FEEDER CABLE NOT PROPERLY SUPPORTED
OPEN 08/22/2016 08/22/2016
 
004 (999) OTHER
(GROUND FLOOR)M.C GROUND CONDUCTORS TERMINATED ON NEUTRAL BAR NOT PERMITTED
OPEN 08/22/2016 08/22/2016
 
005 (999) OTHER
(GROUND FLOOR) ARC FAULT STICKER MISSING ON ELECTRICAL EQUIPMENT
OPEN 08/22/2016 08/22/2016
 
006 (999) OTHER
(GROUND FLOOR)RECEPTACLES SERVING FOOD PREPARATION AREA NOT GFCI PROTECTED
OPEN 08/22/2016 08/22/2016
 
007 (999) OTHER
(GROUND FLOOR)M.C CABLE NOT TERMINATED WITH APPROVED CONNECTOR FOR HOT WATER TANK
OPEN 08/22/2016 08/22/2016
 
008 (999) OTHER
(GROUND FLOOR) HOT WATER CIRCUIT NOT SIZED PROPERLY
OPEN 08/22/2016 08/22/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Electrical Applications  |  Back