BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A263248
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 5-19 BORDEN AVENUE QUEENS BIN: 4539589     Block: 34   Lot: 14
   
Application Completed and Certified

Filed: 5-19 BORDEN AV Census Tract:   7 Health Area:  0720
ALL BUILDING Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
Related Job Number:    402497810
DOB Cross Street(s):    5 STREET,    QUEENS MIDTOWN TUNNEL
Status:   C - JOB IS SIGNED OFF 04/03/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/09/2007 7:03 PM
Application Entered:   11/09/2007 Job Start Date:   11/10/2007
Last Change:   04/03/2012 Job End Date:   11/20/2008
Appointment Status:   
Last Inspection By:   THEODORE JUNSCH       On     03/27/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 010786 Licensee Name: JOE ZAGO
Firm: 004257 Firm Name: ROMA ELECTRIC CORP
Firm Phone: 718-777-7662  Firm Address: 30-75 14TH STREET ASTORIA NY 11102 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
010786 ZAGO, JOE 003185 COMPSEC ELECTRIC CORP.

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
2 - TEMPORARY CONSTRUCTION
6 - GENERAL WIRING
Total Fee:  $4,237.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:        Submittal #:   
Owner / Occup: JIM PLOTKIN
Owner Business Name: 525 BORDEN ASSOCIATES, LP
Authorized Representative:  RONI BENJAMINI
Relationship To Owner:   GC


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  400A 3PH
D. 601 Up to 1200 AMPS  1  1200A 3PH
E. Over 1200 AMPS  1  2000A 3PH
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  4-#3/0
D. Over 250 MCM  8  4-500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  50  100A 1PH
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  26  150A 1PH
C. 3 Phase Up to 225 AMPS  2  200A
D. 3 Phase Over 225 AMPS  2  400A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 540  900    320  540     600           
Total Units : 2900 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 76 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 77 - Removed Meters 0 = Total Meters 77

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/09/2007 Notice:  
Power Issued: 11/09/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  I WILL BE WIRING ALL BUILDING (LIGHT & POWER)INCLUDING NEW SERVICE.

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: A263248
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/18/2010 11/30/2010 EBT J E (150) (0) Y
INSPECTION COMMENTS: CHANGE AFCI TO MATCH PANEL ON UPPER FLOORS,RELOCATE SWITCH BOX IN BASEMENT THAT'S BEHIND PIPE,GET PERMISSION FOR LB TO BE IN STAIRWELL FROM ADVISORY BOARD
 
(2) 03/27/2012 04/03/2012 TJ1 C E (60) (0) Y
INSPECTION COMMENTS: CERTIFICATE




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order