NYC Department of Buildings
Electrical Application Details for App #: B403290
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 4907 13 AVENUE BROOKLYN BIN: 3328613     Block: 5642   Lot: 5
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 4909 13 AV Census Tract:   236 Health Area:  6800
13TH AVE Admin Area:   B - BROOKLYN Inspection Area:   J
BROOKLYN, NY 11219 Community Board:   312
Related Job Number:    321144980
DOB Cross Street(s):    49 STREET,    50 STREET
Status:   C - JOB IS SIGNED OFF 11/05/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/09/2015 4:13 PM
Application Entered:   11/09/2015 Job Start Date:   11/09/2015
Last Change:   11/05/2016 Job End Date:   07/25/2016
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     10/07/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012720 Licensee Name: AKIVA MITTELMAN
Firm: 004560 Firm Name: PRIME ELECTRICAL CORP
Firm Phone: 718-484-4383  Firm Address: 5120 13TH AVENUE, 3RD FLOOR BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $552.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  321144980
Building Used As:   K - Store
Store / Other:   SUPERMARKET
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: YOEL WEISS
Owner Business Name: MEGA 53
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  2 SETS #350 MCM
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  2  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10                 
001    40  20    10               
ROF        13      14  136         
Buildings Total 50  25  13  15       136           
Total Units : 239 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/09/2015 Notice: C - CALL TO OFFICE 09/19/2016
Power Issued: 11/09/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: B403290
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/23/2016 05/24/2016 CJE V (148) (6)
INSPECTION COMMENTS: CORRECT ALL OBJECTIONS
 
(2) 07/20/2016 07/20/2016 EID J Y (44) (0)
INSPECTION COMMENTS: FINAL INSPECTION COMPLETED. OBJECTIONS EXIST
 
(3) 09/16/2016 09/19/2016 JTE H X (30) (0) Y
INSPECTION COMMENTS: OPEN OBJECTIONS REMAIN.
 
(4) 10/07/2016 10/11/2016 JTE C R (35) (0)
INSPECTION COMMENTS: INSPECTION PASSED, OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: B403290
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (175) NO FENCE/BARRIER AROUND EQUIPMENT OVER 600V
(BASEMENT)SERVICE FEEDERS RAN IN PARALLEL. ONE SET OF 350 RAN WITH 3/0 GROUNDCONDUCTOR. ART. 310.4(B3)
RSLV 05/23/2016 05/23/2016 10/07/2016
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT) ELECTRIC DISCHARGE FIXTURE NOT GROUNDED. ART. 410.46
RSLV 05/23/2016 05/23/2016 07/20/2016
 
003 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(BASEMENT)ELECTRIC DISCHARGE FIXTURE INSTALLED WITHOUT QUICK DISCONNECT. ART.410.130(G1)
RSLV 05/23/2016 05/23/2016 10/07/2016
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) G.E.C. NOT PROPERLY INSTSLLED. ART. 250.24(C)
RSLV 05/23/2016 05/23/2016 07/20/2016
 
005 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF) AC #6 OVERCURRENT PROTECTION IS OVER THE MAX. ART. 240.3
RSLV 05/23/2016 05/23/2016 07/20/2016
 
006 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ROOF)RECEPTACLE INSTALLED IN WET LOCATION NOT IN AN ENCLOSURE THAT ISWEATHER PROOF. ART. 406.(B1)
RSLV 05/23/2016 05/23/2016 07/20/2016