BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M347238
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 56 LEONARD STREET MANHATTAN BIN: 1088646     Block: 176   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 56 LEONARD ST Census Tract:   33 Health Area:  7700
ALL FLOORS SERVED,MR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
Related Job Number:    104799648
DOB Cross Street(s):   WEST BROADWAY,    CHURCH STREET
Status:   C - JOB IS SIGNED OFF 11/12/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/06/2013 7:59 PM
Application Entered:   11/06/2013 Job Start Date:   12/15/2013
Last Change:   11/12/2019 Job End Date:   12/15/2016
Appointment Status:   
Last Inspection By:   RIVERA, F       On     11/12/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $2,492.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KEYVAN KAZEMI
Owner Business Name: ALEXICO GROUP LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  7  ELEVATORS
B. Each Additional 10 Floors Or Less  19  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/18/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M347238
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/13/2019 07/13/2019 CDX V (300) (11)
INSPECTION COMMENTS: FAIL. ELECTRICAL CONTRACTOR NOT SHOW UP. ELEVATOR CONTRACTOR PRESENT ON INSPECTION. ( BY ELEVATOR CONTRACTOR COMMENTS, NOT ALLOWED TO OPEN ANY ELECTRICAL EQUIPMENT)
 
(2) 10/17/2019 10/18/2019 TOR V R (20) (1)
INSPECTION COMMENTS: FAIL
 
(3) 11/12/2019 11/12/2019 FRI C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000026234

OBJECTION FOR APPLICATION #: M347238
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(ALL FLOORS)TOP OF CAR 110.12(A) KO'S ARE NOT CLOSED ( CONTROL BOX) ELEVATOR ID# 1P48960
RSLV 07/13/2019 07/13/2019 10/17/2019
 
002 (999) OTHER
(ALL FLOORS)620.25 GFCI NOT WORK ( INSIDE ELEVATOR CONTROL CAR ) ELEVATOR ID #1P48960-1P47783-1P47787-1P47788
RSLV 07/13/2019 07/13/2019 10/17/2019
 
003 (999) OTHER
(ALL FLOORS)ALL MOTORS AND LIGHTS CAB DISCONNECT SW , NEEDS FULL INSPECTION , NOACCESS ( SEE COMMENTS) ELEVATORS:1P48960-1P47783-1P47784-1P47784-1P47785-1P47786-1P47787-1P47788
RSLV 07/13/2019 07/13/2019 10/17/2019
 
004 (999) OTHER
(ALL FLOORS)620.22 NOT ACCESS FOR OF CAR . ELEVATOR 1P47783 ( FULL INSPECTION)
RSLV 07/13/2019 07/13/2019 10/17/2019
 
005 (999) OTHER
(CELLAR)CELLAR 620.24 GFCI DOES NOT WORK PIT ELEVATOR: ID # 1P 48960
RSLV 07/13/2019 07/13/2019 10/17/2019
 
006 (999) OTHER
(CELLAR)CELLAR 620.24 (PIT) LIGHTS AND GFCI NOT WORK. ELEVATOR 1P47786
RSLV 07/13/2019 07/13/2019 10/17/2019
 
007 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(ROOF) ROOF ( ELEVATOR ROOM) KO'S ARE NOT CLOSED ( TROUGH)
RSLV 07/13/2019 07/13/2019 10/17/2019
 
008 (999) OTHER
(ROOF)ROOF ( ELEVATOR ROOM) 620.53 NOT PROVIDED IDENTIFICATION ID ( FROMNYC) , NOT PROVIDED IDENTIFICATION OF THE SUPPLY SIDE OCPD (DISCONNECT LIGHTS CAB) ELEVATOR ID#1P48960
RSLV 07/13/2019 07/13/2019 10/17/2019
 
009 (999) OTHER
(ROOF)ROOF ( ELEVATOR ROOM) 620.53 NOT PROVIDED SIGN TO IDENTIFY THELOCATION OF THE SUPPLY SIDE OCPD ( DISCONNECT LIGHT CAB) ELEVATOR ID# 1P48960-1P47783-1P47784-1P47785-1P47786-1P47786-1P47787-1P47788
RSLV 07/13/2019 07/13/2019 10/17/2019
 
010 (999) OTHER
(ROOF)ROOF ( ELEVATOR ROOM) 620.23 MOTOR DISCONNECT SW NOT PROVIDED IDIDENTIFICATION ( NYC) ELEVATOR 1P47784-1P47783
RSLV 07/13/2019 07/13/2019 10/17/2019
 
011 (999) OTHER
(ROOF) ROOF ( ELEVATOR ROOM) 620.53, 620.55 NOT PROVIDED MOTORDISCONNECTING . ELEVATOR 1P 47787-1P47786
RSLV 07/13/2019 07/13/2019 10/17/2019
 
012 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
(ALL FLOORS) MOTORS NOT LISTED T-OUT
RSLV 10/17/2019 10/17/2019 11/12/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.