Electrical Application Details for App #: M399730
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 42 WEST 13 STREET MANHATTAN BIN: 1009613     Block: 576   Lot: 16
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 42 W 13 ST Census Tract:   63 Health Area:  5700
4B/4C Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 03/09/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/04/2017 4:02 PM
Application Entered:   08/04/2017 Job Start Date:   08/04/2017
Last Change:   03/09/2018 Job End Date:   08/04/2018
Appointment Status:   
Last Inspection By:   ALBERT HANSON       On     03/09/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011793 Licensee Name: JEONG YUNG
Firm: 003404 Firm Name: INTELOGIC ELECTRIC, INC.
Firm Phone: 718-768-3188  Firm Address: 254 40TH STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $98.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WING TSANG
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  16 CIRCUIT, 220 VOLT, SIN
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  4B/4C  10  34    16  10         
004  4C    28    13             
Buildings Total 10  62    29  18              
Total Units : 122 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/26/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M399730
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/12/2018 02/12/2018 CBK N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR SHOWED UP BUT DID NOT GET ACCESS.
 
(2) 02/26/2018 02/26/2018 AYC V (51) (4)
INSPECTION COMMENTS: FAIL
 
(3) 03/05/2018 03/05/2018 ATH J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000003348
 
(4) 03/09/2018 03/09/2018 ATH J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000003554
 
(5) 03/09/2018 03/09/2018 ATH J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000003555
 
(6) 03/09/2018 03/09/2018 ATH C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000003556

OBJECTION FOR APPLICATION #: M399730
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (218) UNAPPROVED FIXTURES INSTALLED IN ALL CLOTHES CLOSETS
(FLOOR: 004)LIGHT FIXTURE IN THE CLOTHES CLOSET IS NOT ENCLOSED. ART. 410.16
RSLV 02/26/2018 02/26/2018 03/09/2018
 
002 (229) SPLICE BOXES NOT ACCESSIBLE
(FLOOR: 004)JUNCTION BOXES FOR BOTH APARTMENT PANEL FEEDERS ARE NOT READILYACCESSIBLE. ART. 314.29
RSLV 02/26/2018 02/26/2018 03/09/2018
 
003 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
(FLOOR: 004)FIXTURE IN THE SHOWER AREA IS NOT RATED FOR WET LOCATIONS. ART.410.10
RSLV 02/26/2018 02/26/2018 03/09/2018
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 004)BRANCH CIRCUITS NOT IDENTIFIED AT THE PANELS. ART. 110.3
RSLV 02/26/2018 02/26/2018 03/05/2018