BIS Menu  |  Elevators  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B417924
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 141 LIVINGSTON STREET BROOKLYN BIN: 3000428     Block: 154   Lot: 28
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 141 LIVINGSTON ST Census Tract:   37 Health Area:  2400
MOTOR ROOM Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   BOERUM PLACE,    SMITH STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/28/2016 8:25 AM
Application Entered:   09/28/2016 Job Start Date:   12/01/2016
Last Change:   08/22/2025 Job End Date:   12/31/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   NAJI PHILLIIPS       On     09/20/2018      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 013229 Licensee Name: MARIO BIANCHI
Firm: 000121 Firm Name: AMER. ELEVATOR & MACH. CO
Firm Phone: 718-784-0101  Firm Address: 36-36 33RD STREET, STE 104 LONG ISLAND CITY NY 11106 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
010030 HOOVER, JOHN R 000121 AMER. ELEVATOR & MACH. CO

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $415.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MELINDA JANKELOVITZ
Owner Business Name: CLIPPER REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  3  $625
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 09/24/2018
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: B417924
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/20/2018 09/24/2018 NJP V (105) (9)
INSPECTION COMMENTS: CORRECT OBJECTIONS

OBJECTION FOR APPLICATION #: B417924
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)ELEVATOR CAR TOP PE2 UNUSED OPENINGS / OUTLET BOXES NOT COVERED(ARTICLE 112.10A/ ARTICLE 314.25)
OPEN 09/20/2018 09/20/2018
 
002 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(ROOF) DEFECTIVE EMERGENCY LIGHT ELEVATOR ROOM (AMEND 110.2A)
OPEN 09/20/2018 09/20/2018
 
003 (315) CONDUCTORS NOT PROPERLY IDENTIFIED
(ROOF) CONDUCTOR PHASES NOT PROPERLY IDENTIFIED (ART 200.6)
OPEN 09/20/2018 09/20/2018
 
004 (999) OTHER
(ROOF) LIGHTING DISCO USED AS SPLICE BOX
OPEN 09/20/2018 09/20/2018
 
005 (999) OTHER
(ROOF)UNUSED OPENINGS / OUTLET BOXES NOT COVERED (ARTICLE 112.10A/ ARTICLE314.25)
OPEN 09/20/2018 09/20/2018
 
006 (999) OTHER
(ROOF) GFCI RECEPTECLE NOT PROPERLY FASTEND IN ELEV CAR 4
OPEN 09/20/2018 09/20/2018
 
007 (999) OTHER
(ROOF)MULTI WIRE BRANCH CIRCUIT IN ELEVATOR PANEL DOES NOT SIMULTANEOUSTRIP( ART 210.4B)
OPEN 09/20/2018 09/20/2018
 
008 (999) OTHER
(ROOF) ELEVATOR PANEL NOT IDENTIFIED
OPEN 09/20/2018 09/20/2018
 
009 (999) OTHER
(ROOF)PE1 ELEVATOR PANEL GROUND NOT IDENTIFIED/ TERMINATED (ART 200.6) /110.14
OPEN 09/20/2018 09/20/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.