Electrical Application Details for App #: M328931
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 301 EAST 63 STREET MANHATTAN BIN: 1044384     Block: 1438   Lot: 1
   
Application Completed and Certified

Filed: 1202 2 AV Census Tract:   110 Health Area:  4900
1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):   EAST 63 STREET,    EAST 64 STREET
Status:   C - JOB IS SIGNED OFF 03/23/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/26/2012 6:03 PM
Application Entered:   06/26/2012 Job Start Date:   06/26/2012
Last Change:   03/23/2013 Job End Date:   06/25/2013
Appointment Status:   
Last Inspection By:   AGELONIAS, ANASTASIOS       On     03/18/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011392 Licensee Name: HOWARD M LEUNG
Firm: 003536 Firm Name: AERO ELECTRIC CORP
Firm Phone: 212-673-4383  Firm Address: 78 FORSYTH STREET, STE 1 NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $91.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   HEALTH STORE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BABAIAN VAHIK
Owner Business Name: THE HEALTH NUTS INC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20-1 POLE
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    80  32    20  20         
Buildings Total 80  32    20     20           
Total Units : 157 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/05/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  TO REPLACE PANEL

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M328931
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/27/2013 03/05/2013 LBI A (60) (7) Y
INSPECTION COMMENTS: SCOPE OF JOB IS DELI /JUICE BAR AREA NOT ENTIRE STORE
 
(2) 03/18/2013 03/23/2013 IOS C R (25) (0) Y
INSPECTION COMMENTS: X

OBJECTION FOR APPLICATION #: M328931
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PNL NEW MULTIWIRE CKTS-NO SIMULATANEOUS MEANS OF DISCONNECT 210.4 (B)
RSLV 02/27/2013 02/27/2013 03/18/2013
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
1 FLR REFRIG.COMPRESSOR TIME CLOCK IN DELI /JUICE BAR AREA 250.110
RSLV 02/27/2013 02/27/2013 03/18/2013
 
003 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
FLR TIME CLOCK NEUTRAL AND EQUIP.GRD FOR SJ IMPROPERLY SPLICED 110.14(B)
RSLV 02/27/2013 02/27/2013 03/18/2013
 
004 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
1FL TRACK LIGHTING CHASE NIPPLES NOT MAKING CONTRACT WITH BOX RACEWAY SYSTEM
RSLV 02/27/2013 02/27/2013 03/18/2013
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
1FL DELI CASE RECEPTACLES NOT GFCI,PROTECTED PER MANUFACTURES SPEC 2210.8
RSLV 02/27/2013 02/27/2013 03/18/2013
 
006 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
ROOF EQUIPMENT GRD FOR REFRIG COMPRESSORS UNDERSIZED PER.TABLE 250.122
RSLV 02/27/2013 02/27/2013 03/18/2013
 
007 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
ROOF IMPROPER TERMINATION OF EQUIP GRDS IN JUCTION BOX FOR COMPRESSORS 250.8.110.14
RSLV 02/27/2013 02/27/2013 03/18/2013