BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M353688
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 104 CHARLTON STREET MANHATTAN BIN: 1010370     Block: 597   Lot: 7502
   
Application Completed and Certified

Filed: 104 CHARLTON ST Census Tract:   37 Health Area:  6800
1 E FRONT Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10014 Community Board:   102
Special Place Name:   P360 SPACES LLC
DOB Cross Street(s):   HUDSON STREET,    GREENWICH STREET
Status:   C - JOB IS SIGNED OFF 10/31/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/14/2014 6:34 AM
Application Entered:   05/14/2014 Job Start Date:   05/14/2014
Last Change:   10/31/2014 Job End Date:   05/02/2015
Appointment Status:   
Last Inspection By:   ELLIS DAVID       On     10/15/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011440 Licensee Name: MARIO F CASTRO
Firm: 004009 Firm Name: POWER SURGE ELECTRIC, INC
Firm Phone: 718-276-9797  Firm Address: 122-20 MONTAUK STREET SPRINGFIELD GARDENS NY 11413 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $67.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: HUNG M NGUYEN
Owner Business Name: P360 SPACES LLC
Authorized Representative:  HUNG NGUYEN
Relationship To Owner:   ELECT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  8 AWG, A/C
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  30  20  30             
Buildings Total 30  20  30                
Total Units : 86 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/29/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  A/C, LIGHTS AND REC..

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M353688
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/23/2014 09/29/2014 LBI A (30) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 10/15/2014 10/21/2014 EID C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M353688
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
1 FL. GFCI NOT PROVIDED FOR PANTRY PLUGMOLS ABVE SINK. 210.8B
RSLV 09/23/2014 09/23/2014 10/15/2014
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
1 FL. ROOFTOP AC UNIT OVER FUSED PER NAMEPLATE. 422.11A
RSLV 09/23/2014 09/23/2014 10/15/2014
 
003 (999) OTHER
ROOF SERVICE RECEPTACLE NOT PROVIDED FOR AC UNIT. 210.63
RSLV 09/23/2014 09/23/2014 10/15/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back