BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M346342
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 47 5 AVENUE MANHATTAN BIN: 1009274     Block: 569   Lot: 4
   
Application Completed and Certified

Filed: 47 5 AV Census Tract:   61 Health Area:  5700
GROUND Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):   EAST 11 STREET,    EAST 12 STREET
Status:   C - JOB IS SIGNED OFF 07/23/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/14/2013 11:19 AM
Application Entered:   10/14/2013 Job Start Date:   10/14/2013
Last Change:   07/23/2014 Job End Date:   10/14/2013
Appointment Status:   
Last Inspection By:   SCHUSZTER, NORBET       On     07/17/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012170 Licensee Name: IVAN BUTKOVIC
Firm: 003881 Firm Name: EINSTEIN ELEC'L CORP
Firm Phone: 718-274-7600  Firm Address: 42-16 28TH AVENUE, 2ND FL ASTORIA NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $158.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN NEWTON
Owner Business Name: SALMAGUNDI CLUB
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  4X4/0
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  GR  55  20    10               
Buildings Total 55  20    10                  
Total Units : 85 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/11/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M346342
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/30/2014 07/11/2014 ECH A (45) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 07/17/2014 07/23/2014 NRS C R (10) (0) Y
INSPECTION COMMENTS: FUSES ARE EXISTING

OBJECTION FOR APPLICATION #: M346342
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
CELLAR WATER METER NOT JUMPED 250.53
RSLV 06/30/2014 06/30/2014 07/17/2014
 
002 (999) OTHER
ROOF GFI FOR HVAC NOT WEATHER RESISTANT 406.88
RSLV 06/30/2014 06/30/2014 07/17/2014
 
003 (999) OTHER
CELLAR FUSE MARKINGS FOR SERVICE SWITCH 110.21
RSLV 06/30/2014 06/30/2014 07/17/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order