BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M364897
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 431 EAST 52 STREET MANHATTAN BIN: 1040154     Block: 1364   Lot: 17
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 431 E 52 ST Census Tract:   86.03 Health Area:  5000
BASE., FLOORS 1 -5 Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10022 Community Board:   106
DOB Cross Street(s):    1 AVENUE,    DEAD END
Status:   C - JOB IS SIGNED OFF 10/16/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/17/2015 10:00 AM
Application Entered:   03/17/2015 Job Start Date:   03/18/2015
Last Change:   10/16/2018 Job End Date:   10/19/2015
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     09/13/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011928 Licensee Name: DAVID C PASQUERELLA
Firm: 003569 Firm Name: DAY ELEC'L CONTR'G CORP
Firm Phone: 718-994-7769  Firm Address: 3524 ROMBOUTS AVENUE BRONX NY 10475 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $336.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JULIUS ZACHARY
Owner Business Name: WHITE PEACOCK LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    15  20    10               
001    12    10               
002    15                 
003    15  16    12               
004    16                 
005    14                 
Buildings Total 53  93    50                  
Total Units : 196 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/17/2015 Notice: 1 - FIRST NOTICE 04/09/2018
Power Issued: 03/17/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M364897
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/03/2017 12/04/2017 CBK V (60) (11)
INSPECTION COMMENTS: SEE OBJECTION DETAILS. CONTRACTOR INSTALLED ONE SERVICE SWITCH.
 
(2) 03/24/2018 03/26/2018 CLC N (11) (0) Y
INSPECTION COMMENTS: CONTR. NO SHOW, NO ACCESS
 
(3) 03/28/2018 03/29/2018 STP V Y (35) (2)
INSPECTION COMMENTS: FAIL.
 
(4) 04/06/2018 04/09/2018 AYC V R (112) (1)
INSPECTION COMMENTS: FAIL
 
(5) 09/13/2018 09/13/2018 BMP C R (40) (0)
INSPECTION COMMENTS: OBJECTION REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M364897
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(FLOOR: 004) RECEPTACLES NOT WORKING IN BATH ROOM.
RSLV 12/03/2017 12/03/2017 03/28/2018
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 004) OPEN BOXES IN BAR AREA.
RSLV 12/03/2017 12/03/2017 03/28/2018
 
003 (999) OTHER
(FLOOR: 004)BAR RECEPTACLE BOXES SET IN COMBUSTIBLE MATERIALS. 210.4
RSLV 12/03/2017 12/03/2017 03/28/2018
 
004 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
(FLOOR: 005)PANELS AND DISCONNECT SWITCH IN ELEVATOR MACHINE ROOM HAVE WHITEWIRES ON GROUND BARS.
RSLV 12/03/2017 12/03/2017 04/06/2018
 
005 (999) OTHER
(FLOOR: 005) BALCONY RECEPTACLES NOT WR. 406.8
RSLV 12/03/2017 12/03/2017 03/28/2018
 
006 (999) OTHER
(FLOOR: 005) CLOSET WITH EXTENSION CORD FOR CABLE BOX. 400.8
RSLV 12/03/2017 12/03/2017 03/28/2018
 
007 (999) OTHER
(FLOOR: 005) BALCONY RECEPTACLE NOT GFCI PROTECTED. 210.8
RSLV 12/03/2017 12/03/2017 04/06/2018
 
008 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(BASEMENT) SERVICE SWITCH NOT PROPERLY GROUNDED AND BONDED.
RSLV 12/03/2017 12/03/2017 04/06/2018
 
009 (273) GROUND CLAMP NOT ACCESSIBLE
(BASEMENT) NO ACCESS TO GROUND ROD CONNECTION.
RSLV 12/03/2017 12/03/2017 03/28/2018
 
010 (999) OTHER
(BASEMENT) BX CONNECTOR USED ON FLEX CORD FOR DRIVER. 110.3
RSLV 12/03/2017 12/03/2017 03/28/2018
 
011 (999) OTHER
(BASEMENT)GROUPING AND BREAKER TIES NEEDED IN BOILER ROOM PANEL. 210.4
RSLV 12/03/2017 12/03/2017 03/28/2018
 
012 (999) OTHER
(FLOOR: 005) SERVICE ENTRANCE BONDING PER NEC 250.102
RSLV 03/28/2018 03/28/2018 04/06/2018
 
013 (999) OTHER
(FLOOR: 005) BOILER RM PANEL IDENTIFY EGC PER NEC 250.119
RSLV 03/28/2018 03/28/2018 04/06/2018
 
014 (999) OTHER
(BASEMENT)MAIN SERVICE DISCONNECT ENCLOSURE IS NOT RATED FOR SERVICE EQUIPMENTUSE. ART. 110.3
RSLV 04/06/2018 04/06/2018 09/13/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.