BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A347910
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 140-26 FRANKLIN AVENUE QUEENS BIN: 4458036     Block: 5182   Lot: 9
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 140-26 FRANKLIN AV Census Tract:   857 Health Area:  1200
ROOF Admin Area:   A - QUEENS Inspection Area:   B
QUEENS, NY 11355 Community Board:   407
Special Place Name:   FLUSHING
DOB Cross Street(s):   KISSENA BOULEVARD,    UNION STREET
Status:   C - JOB IS SIGNED OFF 12/22/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/11/2016 9:51 PM
Application Entered:   04/11/2016 Job Start Date:   04/12/2016
Last Change:   12/22/2016 Job End Date:   03/11/2017
Appointment Status:   
Last Inspection By:   BASDEO, C       On     12/16/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011316 Licensee Name: RALPH J RUSSO
Firm: 002733 Firm Name: RJ RUSSO ELECTRIC CO.
Firm Phone: 718-423-4742  Firm Address: 45-57 BELL BLVD BAYSIDE NY 11361 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
E - SUSTAINABLE ENERGY - SOLAR
Total Fee:  $268.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: FRANKLIN AVE REALTY CO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  2-200 AMPS
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  2-4 #6WIRES
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1-4#3/0 WIRES
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1-200 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                      129 
ROF              174  54         
Buildings Total              54          129 
Total Units : 183 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/02/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SOLAR INSTALL,174 310 WATT SOLAR MODULES,2 ARRAYS 5 STRINGS,2 INVERTERS,1 PANEL,1 TRANSFORMER,2 AC DISCONNECTS.TOTAL 53.94 KW

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: A347910
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/17/2016 11/17/2016 COB V (60) (2)
INSPECTION COMMENTS: OBJECTIONS ISSUED
 
(2) 12/01/2016 12/02/2016 COB V R (30) (1)
INSPECTION COMMENTS: NEW OBJECTION ISSUED
 
(3) 12/16/2016 12/16/2016 COB C R (5) (0)
INSPECTION COMMENTS: OBJECTION REMOVED AS PER EMAIL FROM ADVISORY BOARD, CONDUIT IN DAMP LOCATION

OBJECTION FOR APPLICATION #: A347910
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT)480V DISCONNECT, EQUIPMENT GROUNDING CONDUCTOR TO BE BONDED TOENCLOSURE
RSLV 11/17/2016 11/17/2016 12/01/2016
 
002 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(ROOF)ROOF AND BASEMENT, SPECIAL PERMISSION REQUIRED TO INSTALL 480VEQUIPMENT IN RESIDENTIAL BUILDING
RSLV 11/17/2016 11/17/2016 12/01/2016
 
003 (999) OTHER
(GROUND FLOOR)EMT USED OUTSIDE IN NOT FULLY ENCLOSED GARAGE - 358.12 NYC AMENDMENT
RSLV 12/01/2016 12/01/2016 12/16/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order