BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B079466
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 624 PRESIDENT STREET BROOKLYN BIN: 3020236     Block: 958   Lot: 27
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 624 PRESIDENT ST Census Tract:   133 Health Area:  4200
BSMT Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    4 AVENUE,    5 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   01/30/1991 Job Start Date:   01/21/1991
Last Change:   08/22/2025 Job End Date:   01/25/1991
Appointment Status:   
Last Inspection By:   PRIVATE AGENCY       On     05/01/1998      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  

License #: 009927 Licensee Name: M BOJSIUK
Firm: 001224 Firm Name: RAYPALS ELEC'L CORP.
Firm Phone: 718-834-0420  Firm Address: 200 SACKETT STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $58.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: JOSPEH AVER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 5 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: R - REQUESTED Objection Flag:
Power Requested: 01/30/1991 Notice:  
Power Issued: 01/30/1991 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: B079466
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/20/1992 12/08/1992 MX1 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 12/18/1992 01/05/1993 MX1 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(3) 01/25/1993 02/08/1993 MX1 N (15) (0)
INSPECTION COMMENTS: NONE
 
(4) 10/08/1993 07/20/1995 X01 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(5) 04/18/1997 11/25/1997 X01 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(6) 05/01/1998 05/18/1998 X01 N (30) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order