BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M367235
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 308 8 AVENUE MANHATTAN BIN: 1088709     Block: 775   Lot: 7502
   
Application Completed and Certified

Filed: 260 W 26 ST Census Tract:   91 Health Area:  5200
260 W 26TH ST Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
Related Job Number:    122284740
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 09/14/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/11/2015 11:01 AM
Application Entered:   05/11/2015 Job Start Date:   05/11/2015
Last Change:   09/14/2015 Job End Date:   07/07/2015
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     08/10/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011363 Licensee Name: JACOB NAFTALY
Firm: 002781 Firm Name: JACOBS ELECTRIC CORP.
Firm Phone: 718-533-9355  Firm Address: 37-31 58TH STREET, STE A-11 WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $296.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122284740
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRIGHT HORIZONS
Owner Business Name: BRIGHT HORIZONS
Authorized Representative:  GERARD COFFEY
Relationship To Owner:   SUPER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    128  60  40  26  14  40     
Buildings Total 128  60  40  26     14     40      
Total Units : 316 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/11/2015 Notice: 1 - FIRST NOTICE 07/23/2015
Power Issued: 05/11/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  FURNISH AND INSTALL 1 ELECTRICAL PANEL, GENERAL POWER, SWITCHES, OUTLETS AND LIGHTING FIXTURES.

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M367235
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/14/2015 07/23/2015 NRS V G (60) (5) Y
INSPECTION COMMENTS: 30A SPACE HEATER NOT INSPECTED
 
(2) 08/10/2015 08/24/2015 BUR C R E (70) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M367235
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASE ELECTRICAL ROOM NOT FIRE PROOFED
RSLV 07/14/2015 07/14/2015 08/10/2015
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
GR. DISH WASHER RECE. BOX
RSLV 07/14/2015 07/14/2015 08/10/2015
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
GR. RECES. W/ IN 6' SINK
RSLV 07/14/2015 07/14/2015 08/10/2015
 
004 ( 42) BUSHINGS ARE MISSING OR LOOSE
GR. W.H. & W.H. DISCONNECT SWITCH
RSLV 07/14/2015 07/14/2015 08/10/2015
 
005 (999) OTHER
A/C DISCONNECTS: E.G.C DOUBLE LUGGED
RSLV 07/14/2015 07/14/2015 08/10/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back