BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B375558
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 401 BRIDGE STREET BROOKLYN BIN: 3413889     Block: 145   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 503 FULTON ST Census Tract:   15 Health Area:  1100
ALL FLOORS SERVED, MR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   BRIDGE STREET,    HOYT STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/10/2013 9:15 PM
Application Entered:   12/10/2013 Job Start Date:   01/15/2014
Last Change:   08/22/2025 Job End Date:   01/15/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     08/07/2014      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   COMMERCIAL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JASON LABOZ
Owner Business Name: TRIAD FULTON LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  ELEVATORS
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 08/11/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALLATION OF HYDRO FREIGHT ELEVATORS(5&6)BY ELEVATOR COMPANY IN CONJUNCTION WITH ELEVATOR APPLICATION(273018E). POWER TO CONTROL, 110V LIGHTING, MR,PIT GFCI BY OTHERS H3467(229)

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: B375558
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/07/2014 08/11/2014 CJH V (40) (6) Y
INSPECTION COMMENTS: NO ACCESS TO CAR 5.6 NOT LOCATED

OBJECTION FOR APPLICATION #: B375558
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
CELLAR MAIN ELECTRICAL RM LINDEN SIGNS FOR ELEVATORS SWITCHES ATSNOT PROVIDED 620.51 (B)
OPEN 08/07/2014 08/07/2014
 
002 (999) OTHER
CELLAR MAIN ELECTRIC RM WHT USED AS HOT 200.7
OPEN 08/07/2014 08/07/2014
 
003 (999) OTHER
CELLAR MAIN ELECTRIC RM ELEVATOR PANELS CIR NOT GROUPED 210.4D
OPEN 08/07/2014 08/07/2014
 
004 (999) OTHER
CELLAR MAIN ELECTRIC RM ELEVAQTOR PANELS MULTI CIR NEED COMMON TRIP210.4B
OPEN 08/07/2014 08/07/2014
 
005 (999) OTHER
TJ MAXX ELEVATOR RM CAR #6 250.24 (A5)
OPEN 08/07/2014 08/07/2014
 
006 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
TJ MAXX ELEVATOR RM CAR #5 DIS SW GND ISOLATED 250.4 (A)
OPEN 08/07/2014 08/07/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back