DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M281248
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 168 ORCHARD STREET MANHATTAN BIN: 1005348     Block: 411   Lot: 12
   
Application Completed and Certified

Filed: 170 ORCHARD ST Census Tract:   30.01 Health Area:  6600
BSMNT,1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
Related Job Number:    104086695
DOB Cross Street(s):   RIVINGTON STREET,    STANTON STREET
Status:   C - JOB IS SIGNED OFF 08/12/2008
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   07/02/2008 Job Start Date:   06/27/2008
Last Change:   08/12/2008 Job End Date:   08/25/2008
Appointment Status:   
Last Inspection By:   BEST, J       On     08/02/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010695 Licensee Name: JOE YUK LEE
Firm: 002279 Firm Name: UNITED ELEC'L CONT'G CORP
Firm Phone: 212-777-8899  Firm Address: 45-04 162ND STREET, SUITE 205 FLUSHING NY 11385 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: EPICERIE CAFE
Authorized Representative:  JOE LEE
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                 
Total Units : 9 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  06/02/2008
Power Issued: Response: F - FILED TO REMOVE OBJECTION 07/02/2008

Follow-Up: X - FILED APPL,NOW CLOSED 07/02/2008
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M281248
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/27/2008 06/02/2008 SVJ W (1) (11)
INSPECTION COMMENTS: NONE
 
(2) 08/02/2008 08/12/2008 JSB C R (20) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M281248
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SER EQUIPT ENCL ARE NOT BONDED TOGETHER SER SW ALL SW NEUT NOT BONDED (NEW END LINE BOX)
RSLV 05/27/2008 05/27/2008 08/02/2008
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
CIRCUIT OVER CURRENT PROTECTIVE DEVICE IS OF IMPROPER SIZE 20A ON LIGHT BSMT 200A PNL
RSLV 05/27/2008 05/27/2008 08/02/2008
 
003 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
DEFECTIVE FIXTURES ARE IN USE EXIT LIGHT
RSLV 05/27/2008 05/27/2008 08/02/2008
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
FIXED EQUIPT IS NOT PROPERLY GROUNDED BSMT FLUE FIX
RSLV 05/27/2008 05/27/2008 08/02/2008
 
005 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
ARMORED CABLES ARE NOT PROPERLY TERMINATED BSMT
RSLV 05/27/2008 05/27/2008 08/02/2008
 
006 ( 29) OUTLET BOXES ARE NOT COVERED
OUTLET BOXES ARE NOT COVERED THRUOUT BSMT, 1FL
RSLV 05/27/2008 05/27/2008 08/02/2008
 
007 ( 30) OUTLET BOXES ARE NOT SECURED
OUTLET BOXES ARE NOT SECURED BSMT
RSLV 05/27/2008 05/27/2008 08/02/2008
 
008 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
KNOCKOUTS ARE NOT CLOSED IN PNL BOX PNL BSMT & 1FL
RSLV 05/27/2008 05/27/2008 08/02/2008
 
009 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
FIXTURE NOT INSTALLED IN AN APPROVED MANNER FIX 1FL KITCHEN & BSMT
RSLV 05/27/2008 05/27/2008 08/02/2008
 
010 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
PNL HAS NOT BEEN PROVIDED WITH A DIRECTORY BSMT & 1FL
RSLV 05/27/2008 05/27/2008 08/02/2008
 
011 (999) OTHER
MULTI CONNECTIONS ON SINGLE LUG 3025.C BSMT COMPRESSOR PNLARMORED CABLES ARE INSTALLED EXPOSED,REDIRECT FROM CONT.REF M157617
RSLV 05/27/2008 05/27/2008 08/02/2008