Electrical Application Details for App #: M403901
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 432 PARK AVENUE MANHATTAN BIN: 1088817     Block: 1292   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 432 PARK AV Census Tract:   112.02 Health Area:  4800
44C Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
DOB Cross Street(s):   EAST 56 STREET,    EAST 57 STREET
Status:   C - JOB IS SIGNED OFF 10/05/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/08/2017 3:54 PM
Application Entered:   11/08/2017 Job Start Date:   11/09/2017
Last Change:   10/05/2018 Job End Date:   11/09/2018
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     10/05/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010587 Licensee Name: HARRY FRENKEL
Firm: 002697 Firm Name: APOLLO ELECTRIC INC.
Firm Phone: 212-627-2561  Firm Address: 127 WEST 24TH ST,5TH FL STE#A NEW YORK NY 10011 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $239.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LOWELL KRAFF
Owner Business Name: OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
044  44C  232  70  17  46  232             
Buildings Total 232  70  17  46  232                
Total Units : 597 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/06/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M403901
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/03/2018 08/06/2018 DWB V (50) (3)
INSPECTION COMMENTS: OBJECTION ISSUED,
 
(2) 10/05/2018 10/05/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000015629
 
(3) 10/05/2018 10/05/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000015627
 
(4) 10/05/2018 10/05/2018 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000015628

OBJECTION FOR APPLICATION #: M403901
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(FLOOR: 044) 110.12(A), KO SEAL NOT INSTALLED.
RSLV 08/03/2018 08/03/2018 10/05/2018
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 044)210.8, AFCI INSTALLED IN ELECTRICAL PANEL FOR KITCHEN 2 CIRCUITAPPLIANCE ARE DEFECTIVE.
RSLV 08/03/2018 08/03/2018 10/05/2018
 
003 (999) OTHER
(FLOOR: 044)314.20, JUNCTION BOXES SET BACK WITH COMBUSTIBLE MATERIAL INKITCHEN.
RSLV 08/03/2018 08/03/2018 10/05/2018