Electrical Application Details for App #: Y148385
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 2514 COLDEN AVENUE BRONX BIN: 2051683     Block: 4447   Lot: 11
   
Application Completed and Certified

Filed: 2514 COLDEN AV Census Tract:   324 Health Area:  0820
1ST AND 2ND FLOOR Admin Area:   Y - BRONX Inspection Area:   G
BRONX, NY 10469 Community Board:   211
DOB Cross Street(s):   MACE AVENUE,    ALLERTON AVENUE
Status:   C - JOB IS SIGNED OFF 10/21/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/15/2009 9:44 PM
Application Entered:   09/15/2009 Job Start Date:   09/18/2009
Last Change:   10/21/2010 Job End Date:   12/01/2009
Appointment Status:   
Last Inspection By:   PETER CONTEY       On     08/02/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011601 Licensee Name: VITO INGRAVALLO
Firm: 003138 Firm Name: VITO INGRAVALLO
Firm Phone: 718-331-7478  Firm Address: 1448 65TH STREET BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $169.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARCIAL RAMIREZ
Authorized Representative:  MARCIAL COLDEN
Relationship To Owner:   SELF


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  10  21  10  10             
002  10  19  10  10             
Buildings Total 20  40  20  20                
Total Units : 106 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/11/2010
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW EXTENSION WITH 3 BEDROOMS ON 1ST AND 2ND FLOOR

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: Y148385
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/02/2010 06/11/2010 PC2 A (45) (3) Y
INSPECTION COMMENTS: C
 
(2) 08/02/2010 08/10/2010 PC2 C R (40) (0) Y
INSPECTION COMMENTS: C

OBJECTION FOR APPLICATION #: Y148385
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(A) NEC ARTICLE 230.46 1ST FK SERVICE CONDUCTORS FORM METER TO MAINCIRCUIT BREAKERS SPLICED
RSLV 06/02/2010 06/02/2010 08/02/2010
 
002 (999) OTHER
(B) NEC ARTICLE 240.24.A 2ND FLOOR APTS CIRCUIT BREAKERS PANEL MOUNTED ABOVED 6FT 7" FROM FLOOR
RSLV 06/02/2010 06/02/2010 08/02/2010
 
003 (999) OTHER
(C) NEC ARTICLE 110.3.13 1ST FLOOR OUTSIDE DECK RECEPTALES PROVIDEDARE NOT SUITABLE FOR OUTDOOR USE
RSLV 06/02/2010 06/02/2010 08/02/2010