Electrical Application Details for App #: M287821
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 57 GREENE STREET MANHATTAN BIN: 1007297     Block: 486   Lot: 28
   
Application Completed and Certified

Filed: 63 GREENE ST Census Tract:   49 Health Area:  6800
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   BANG AND OLUFSEN
DOB Cross Street(s):   BROOME STREET,    SPRING STREET
Status:   C - JOB IS SIGNED OFF 03/15/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/10/2008 12:39 PM
Application Entered:   12/10/2008 Job Start Date:   12/12/2008
Last Change:   03/15/2010 Job End Date:   12/13/2008
Appointment Status:   
Last Inspection By:   BEST, J       On     03/10/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011355 Licensee Name: CARMINE L LIPPOLIS
Firm: 002775 Firm Name: LIPPOLIS ELECTRIC, INC.
Firm Phone: 718-892-4055  Firm Address: 4459 BRONX BOULEVARD BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $370.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   STEREO
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: VICTOR COLE
Owner Business Name: DCD AMERICA
Authorized Representative:  VICTOR COLE
Relationship To Owner:   LANDLORD


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  400A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/10/2008 Notice: 1 - FIRST NOTICE 05/15/2009
Power Issued: 12/10/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M287821
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/05/2009 02/10/2009 SR2 A G (30) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 05/05/2009 05/15/2009 CCH A R E (60) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(3) 09/29/2009 10/05/2009 SR2 J Y (30) (1) Y
INSPECTION COMMENTS: NONE
 
(4) 12/25/2009 03/04/2010 JSB Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(5) 03/10/2010 03/15/2010 JSB C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M287821
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
ELECT SERV,NO FDR DIAG.(W/LOAD CALCS)FOR INSTALLATION OF NEW 400 AS/S (TRANS "S"),S.E.C.'S;FDRS;3/0 PNL
RSLV 02/05/2009 02/05/2009 05/05/2009
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
400A S/S NO NEUTRAL ENCLOSURE BONDING 400A S/S (TRANS "S")
RSLV 02/05/2009 02/05/2009 05/05/2009
 
003 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
NO ADV.BD APPROV (CAL.#) FOR 400A S/S ADDITION BRINGING TOTAL AMPACITY OF SERVICE TO EXCEDE 1000KVA
RSLV 02/05/2009 02/05/2009 05/05/2009
 
004 (999) OTHER
230.71 MORE THAN SIX SER SW IN USE TOTAL OF 8 S/S COUNTED IN USE WITH ELECTRICIAN & BLDG SUPT
RSLV 02/05/2009 02/05/2009 05/05/2009
 
005 (999) OTHER
SER.ROOM: 200A DIS SW NEUTRAL BONDED250.24A5
RSLV 05/05/2009 09/29/2009 03/10/2010
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
SER.ROOM: 400A S SWITCH NEUTRAL NOT BONDED (TRANS 'S')
RSLV 05/05/2009 05/05/2009 09/29/2009
 
007 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
SER.ROOM: FEEDER NEED LOAD CALCS FOR NEW 400A SER SWITCH
RSLV 05/05/2009 09/29/2009 03/10/2010
 
008 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
NO ADV BD APPROV (CAL #)FOR 400A S/S ADDITION BRINGING TOTAL AMPACITY OF SERVICE TO EXCEDE 1000KVA
RSLV 09/29/2009 09/29/2009 03/10/2010