Electrical Application Details for App #: B347531
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 738 ALBANY AVENUE BROOKLYN BIN: 3327708     Block: 4829   Lot: 1
   
Application Completed and Certified

Filed: 738 ALBANY AV Census Tract:   808 Health Area:  4800
FLOORS 1- 6 Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11203 Community Board:   309
Special Place Name:   WINTHROP AVE & CLARKSON AVE
Related Job Number:    320135607
DOB Cross Street(s):   WINTHROP STREET,    CLARKSON AVENUE
Status:   C - JOB IS SIGNED OFF 10/07/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/27/2012 3:15 PM
Application Entered:   02/27/2012 Job Start Date:   02/27/2012
Last Change:   10/07/2013 Job End Date:   01/31/2013
Appointment Status:   
Last Inspection By:   BEST, J       On     09/23/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010732 Licensee Name: RICHARD F BROWN
Firm: 002997 Firm Name: RELIANT ELEC'L CONT'G INC
Firm Phone: 718-636-8898  Firm Address: 628 CLASSON AVENUE BROOKLYN NY 11238 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   
Owner / Occup: BRUNO FRUSTACI
Owner Business Name: BRUNO FRUSTACI CONT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  5  600 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  1600 AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  114  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  14  350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  114  20 CCT 208V 3 WIRE
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  8  200 AMP 42 CCT 3 PHASE
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  10 HP EACH
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  7  10 HP

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    42  30    24  42  48         
GND    172  156  28  182  172             
002    176  181  33  158  176             
003    176  181  33  158  176             
004    176  181  33  158  176             
005    176  181  33  158  176             
006    176  181  33  158  176             
Buildings Total 1094  1091  193  996  1094     48           
Total Units : 4516 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 114 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 116 - Removed Meters 0 = Total Meters 116

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/27/2012 Notice: 1 - FIRST NOTICE 09/13/2013
Power Issued: 02/27/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: B347531
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/11/2013 09/13/2013 JSB A E (340) (3) Y
INSPECTION COMMENTS: N
 
(2) 09/23/2013 10/07/2013 JSB C R E (180) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B347531
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
FP SVC ENT COND RUN ACCROSS BUS OF ANOTHER SECTION OF SW GEAR 408.3(3) IN SEAL TIGHT
RSLV 09/11/2013 09/11/2013 09/23/2013
 
002 (999) OTHER
BSMT PV DISC FEEDER SEAL TIGHT USED WITHIN SW GEAR 408.3 (3)
RSLV 09/11/2013 09/11/2013 09/23/2013
 
003 (999) OTHER
SEAL TIGHT RUN WITHIN SW SW ENCLOSURE 110.2
RSLV 09/11/2013 09/11/2013 09/23/2013