Electrical Application Details for App #: B373574
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 548 48 STREET BROOKLYN BIN: 3012654     Block: 775   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 548 48 ST Census Tract:   98
CELLAR,BASEMENT,1,2 FLOOR Admin Area:   B - BROOKLYN Inspection Area:   J
BROOKLYN, NY 11220 Community Board:   307
Related Job Number:    320515616
DOB Cross Street(s):    5 AVENUE,    6 AVENUE
Status:   C - JOB IS SIGNED OFF 12/23/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/15/2013 Job Start Date:   09/26/2013
Last Change:   12/23/2017 Job End Date:   12/30/2013
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     12/16/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011777 Licensee Name: ON GUK TSE
Firm: 003385 Firm Name: HI-RITE ELECTRIC CORP
Firm Phone: 718-680-2688  Firm Address: 6508 6TH AVENUE BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $238.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  320515616
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: XIU CHEN
Authorized Representative:   ON GUK TSE
Relationship To Owner:   AUTHORIZED REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  4  4-60A,1- 226V
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  #6 AWG
B. Over #2 to 1/0  1  #110 AWG
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                 
BAS    22  11             
001    22  11             
002    24  11             
Buildings Total 34  76  10  40  34                
Total Units : 194 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 3 + New Meters 4 - Removed Meters 3 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/15/2013 Notice: 1 - FIRST NOTICE 11/28/2017
Power Issued: 10/15/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: B373574
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/04/2017 10/04/2017 JTE V (40) (3)
INSPECTION COMMENTS: INSPECTION FAIL, SEE OBJECTION DETAILS
 
(2) 11/27/2017 11/28/2017 CJH V R (45) (11)
INSPECTION COMMENTS: FAIL
 
(3) 12/16/2017 12/18/2017 DAH C R (14) (0)
INSPECTION COMMENTS: THE VIOLATIONS ARE RESOLVED

OBJECTION FOR APPLICATION #: B373574
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (340) RECEPTACLES NOT TAMPERPROOF
(ALL FLOORS) ALL THROUGHOUT
RSLV 10/04/2017 10/04/2017 11/27/2017
 
002 (134) GROUNDING CONNECTION IS NOT WITHIN 5FT
(BASEMENT) FOR SERVICE EQUIPMENT
RSLV 10/04/2017 10/04/2017 11/27/2017
 
003 (999) OTHER
(OPEN SPACE) ALL OUTDOOR GFCI NOT WR/TR LISTED ART 406.8
RSLV 10/04/2017 10/04/2017 11/27/2017
 
004 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(FLOOR: 001)001 FL BATH LUMINAIRE CABLES NOT PROPERLY TERMINATED 320.40
RSLV 11/27/2017 11/27/2017 12/16/2017
 
005 (999) OTHER
(FLOOR: 001) 001 FL BATH ROOM LUMINAIRE NOT GROUNDED PROPERLY 410.46
RSLV 11/27/2017 11/27/2017 12/16/2017
 
006 (999) OTHER
(FLOOR: 001)001 FL KITCHEN COUNTER TOP RECEPT OUTLETS ZIP SCREWS IN USED 250.8
RSLV 11/27/2017 11/27/2017 12/16/2017
 
007 (282) MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS
(FLOOR: 002) 002,003 FL KITCHEN COUNTER TOP 1 CKT PROVIDED 210.52 B1
RSLV 11/27/2017 11/27/2017 12/16/2017
 
008 (999) OTHER
(FLOOR: 002)002,003 FL SMOKE, LIVING ROOM NOT AFIC PROTECTED 210.12 B
RSLV 11/27/2017 11/27/2017 12/16/2017
 
009 (999) OTHER
(FLOOR: 002) 002 FL PNL CKT BREAKER DEFECTIVE 110.2
RSLV 11/27/2017 11/27/2017 12/16/2017
 
010 (999) OTHER
(ALL FLOORS) THROUGHOUT PNL CKT NOT GROUPED 210.4 D
RSLV 11/27/2017 11/27/2017 12/16/2017
 
011 (999) OTHER
(ALL FLOORS)THROUGHOUT LIVING, BED ROOM WALL SWITCHES NOT ACCESSIBLE 110.2
RSLV 11/27/2017 11/27/2017 12/16/2017
 
012 (999) OTHER
(BASEMENT) BSMT PNL MULTI CKT ON SAME PHASE 210.7 B
RSLV 11/27/2017 11/27/2017 12/16/2017
 
013 (999) OTHER
(BASEMENT) BSMT AC CKT NOT PROVIDED 210.52 (I)
RSLV 11/27/2017 11/27/2017 12/16/2017
 
014 (999) OTHER
(BASEMENT) BSMT LAUNDRY CKT NOT PROVIDED 210.11 C2
RSLV 11/27/2017 11/27/2017 12/16/2017