BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M318766
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 76 EAST 13 STREET MANHATTAN BIN: 1009211     Block: 564   Lot: 45
   

DOB NOW: Inspections


Filed: 132 4 AV Census Tract:   61 Health Area:  5700
EAST 12 STREET & EAST 13 ST. Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):   EAST 12 STREET,    EAST 13 STREET
Status:   K - CLOSED/CANCELLED 06/17/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/16/2011 9:23 AM
Application Entered:   09/16/2011 Job Start Date:   09/16/2011
Last Change:   06/17/2020 Job End Date:   01/28/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SHERON MEYERS       On     06/17/2020      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010118 Licensee Name: ROBERT MARCHISOTTO
Firm: 002914 Firm Name: R.C.M. ELECTRIC CORP.
Firm Phone: 718-339-2680  Firm Address: 1915 MCDONALD AVE. BLDG REAR BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $248.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:   L - FIRE ALARM LOCAL LAW #5
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: W & L GROUP CONSTRUCTION
Authorized Representative:  THOMAS WANG
Relationship To Owner:   PRESIDENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  1  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 07/25/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M318766
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/04/2013 02/07/2013 JVA J (30) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 03/14/2013 03/23/2013 EDB A (60) (15) Y
INSPECTION COMMENTS: ID# 1F10304 AND ELEVATOR ROOM
 
(3) 08/13/2013 08/15/2013 IOS J Y (30) (0) Y
INSPECTION COMMENTS: NONE
 
(4) 07/24/2019 07/25/2019 DWB V X (45) (12)
INSPECTION COMMENTS: ELEVATOR INSPECTED, AND ID # 1F10304, 1P45838, 1P45839, OBJECTION ISSUED.
 
(5) 06/17/2020 06/17/2020 SWR K R (50) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETE. OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M318766
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
ROOF ALL ELEVATOR DISCONNECT SWITCHES; NEUTRAL BONDED 250.24A
RSLV 03/14/2013 03/14/2013 08/13/2013
 
002 (999) OTHER
ROOF 1F10304 DOUBLE LUG NO POWER 110.14 A,3,B
RSLV 03/14/2013 03/14/2013 08/13/2013
 
003 ( 42) BUSHINGS ARE MISSING OR LOOSE
ROOF 1P45839, 1P4T838 DISC SWITCH; BUGHING MISSING 300.4 11
RSLV 03/14/2013 03/14/2013 08/13/2013
 
004 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
ROOF SWITCH GFCI; K/O MISSING 110.12A
RSLV 03/14/2013 03/14/2013 08/13/2013
 
005 (999) OTHER
ROOF IF10304 CONTROL BOX; LB ON TOP, NO ACCESS 110
RSLV 03/14/2013 03/14/2013 08/13/2013
 
006 (999) OTHER
ROOF DOUBLE LUG ON GROUND IN CONTROL BOX 110.14 A, 3B
RSLV 03/14/2013 03/14/2013 08/13/2013
 
007 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
ROOF 1P45835 CDD CONNECTOR NOT APPROVED 110.2 314.25
RSLV 03/14/2013 03/14/2013 08/13/2013
 
008 ( 29) OUTLET BOXES ARE NOT COVERED
ROOF GFCI NO COKER BY CONTROL BOX OF 1P45838 314.25
RSLV 03/14/2013 03/14/2013 08/13/2013
 
009 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
ROOF ALL ELEVATOR MOTOR LOOSE EQUIPMENT GROUND 250.4
RSLV 03/14/2013 03/14/2013 08/13/2013
 
010 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
ROOF PANEL 2P CB MISSING HANDLE TIE
RSLV 03/14/2013 03/14/2013 08/13/2013
 
011 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
ROOF PANEL IN ELEVATOR ROOM; NEUTRAL BONDED A/C CKT 250.24 A
RSLV 03/14/2013 03/14/2013 08/13/2013
 
012 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS)1F10304 TOP OF CAR; DEFECTIVE GFCI WIRING (OPEN GROUND) 110.2A
RSLV 03/14/2013 08/13/2013 06/17/2020
 
013 (178) THERE IS NO LIGHT IN THE ELEVATOR PIT
(ALL FLOORS) 1F10304 PIT NO LIGHT
RSLV 03/14/2013 08/13/2013 06/17/2020
 
014 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
1F10304 PIT; DEFECTIVE GFCI 110.2A
RSLV 03/14/2013 03/14/2013 08/13/2013
 
015 (999) OTHER
1F10304 UNDER CAR NO ACCESS
RSLV 03/14/2013 03/14/2013 08/13/2013
 
016 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(ALL FLOORS)AT EMR, PIT, 250.146, RECEPTACLE INSTALL ARE NOT GROUNDED TO BOXE
RSLV 07/24/2019 07/24/2019 06/17/2020
 
017 (999) OTHER
(ALL FLOORS) ELEVATOR PIT, 620.24(A,B), NO LIGHT IN ELEVATOR.
RSLV 07/24/2019 07/24/2019 06/17/2020
 
018 (999) OTHER
(ALL FLOORS)EMR, 110.16 ARC FLASH LABEL NOT PROVIDED / INSTALL AT ELECTRICALEQUIPMENT.
RSLV 07/24/2019 07/24/2019 06/17/2020
 
019 (999) OTHER
(ALL FLOORS)110.21/22, IDENTIFICATION OF ELEVATOR DIS SW FEEDER, NOTINDENTIFIED.
RSLV 07/24/2019 07/24/2019 06/17/2020
 
020 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(ROOF) AT EMR,110.2(A), RECEPTACLE INSTALL ARE DEFECTIVE.
RSLV 07/24/2019 07/24/2019 06/17/2020
 
021 (212) NO GROUND PROVIDED FOR SEPARATELY DERIVED SYSTEM
(ROOF)250.30, TRANSFORMER/ ELEVATOR VOLTAGE STABILIZER, NOT BOND TO STEEL/BUILDING STRUCTURE.
RSLV 07/24/2019 07/24/2019 06/17/2020
 
022 (220) DOUBLE LUGGING IN SERVICE SWITCH
(ROOF)ALL ELECTRICAL EQUIPMENT, 110.14(A), MULTIPLE CONDUCTOR INSTALL ATSINGLE LUGS.
RSLV 07/24/2019 07/24/2019 06/17/2020
 
023 (302) ELEVATOR MOTORS/CONTROLLERS/ENCLOSURES NOT GROUNDED
(ROOF)AT EMR, ALL, 620.82, ELEVATOR CONTROLLER NOT BOND TO EQUIPMENT,THRU-OUT.
RSLV 07/24/2019 07/24/2019 06/17/2020
 
024 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ROOF) 358.30, EMT CONDUIT NOT SUPPORTED.
RSLV 07/24/2019 07/24/2019 06/17/2020
 
025 (999) OTHER
(ROOF) EMR, ALL, AM 600.7, ELEVATOR CAR LIGHT DIS SW, CONDUCTOR IMPROPERSIZE, 14 AWG USED.
RSLV 07/24/2019 07/24/2019 06/17/2020
 
026 (999) OTHER
(ROOF) 250.110, EQUIPMENT BONDING, CAR LIGHT DIS SW, NOT GROUNDED,THRU-OUT.
RSLV 07/24/2019 07/24/2019 06/17/2020
 
027 (999) OTHER
(ROOF) 348.60, FMC BONDING REQUIRE AT MOTOR, THRU-OUT.
RSLV 07/24/2019 07/24/2019 06/17/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back