NO PLUMBING INSPECTIONS OPEN FOR THIS PROPERTY
Premises: 41 HENRY STREET MANHATTAN BIN: 1003407     Block: 280   Lot: 10
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 41 HENRY ST Census Tract:   8 Health Area:  7800
41 HENRY ST. / BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   CATHERINE STREET,    MARKET STREET
Status:   C - JOB IS SIGNED OFF 06/18/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/02/2015 10:57 PM
Application Entered:   02/02/2015 Job Start Date:   02/03/2015
Last Change:   06/18/2016 Job End Date:   02/02/2016
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     08/27/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012494 Licensee Name: LUIS RIOS
Firm: 004306 Firm Name: LESLU ELECTRIC CORP
Firm Phone: 718-275-1603  Firm Address: 97-24 63RD ROAD REGO PARK NY 11374 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $266.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 20 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PIAMENTA JACK
Owner Business Name: SILVER SHORE PROPERTIES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  TWO 100AMP MAIN BK. DISCO
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  ONE 400A S.S. DISCONNECT
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  TWO SEPARATE SETS OF #2 C
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  ONE SET OF 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 22 #4-Wire 0 #10-Wire 0
Existing Meters 23 + New Meters 22 - Removed Meters 23 = Total Meters 22

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/02/2015 Notice: 1 - FIRST NOTICE 06/11/2015
Power Issued: 02/02/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WE ARE ONLY INSTALLING THE ELECTRICAL SERVICE FOR THIS PREMISSES IN THE BASEMENT.

 
Inspection Details
 

*NO PLUMBING INSPECTIONS OPEN FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: M363276
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/02/2015 06/11/2015 NRS A G (55) (7) Y
INSPECTION COMMENTS: BASEMENT PANEL & STORE DISCONNECT & RISERS FOR APARTMENTS BY OTHERS
 
(2) 08/27/2015 09/01/2015 BUR C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M363276
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASE E.B.J NOT AS PER 250.66
RSLV 06/02/2015 06/02/2015 08/27/2015
 
002 (999) OTHER
BASE G.E.C. NOT AS PER 250.66
RSLV 06/02/2015 06/02/2015 08/27/2015
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BASE NOT AS PER 250.66
RSLV 06/02/2015 06/02/2015 08/27/2015
 
004 (279) WATER METER JUMPER IS MISSING/IMPROPER
BASE NOT AS PER 250.66
RSLV 06/02/2015 06/02/2015 08/27/2015
 
005 (999) OTHER
BASE SUPPLEENTAL GROUND CONDUIT NOT CONTINOUS 250.66 (E)
RSLV 06/02/2015 06/02/2015 08/27/2015
 
006 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
2.5" ON CEILING & G.E.C. CONDUIT IN WELL
RSLV 06/02/2015 06/02/2015 08/27/2015
 
007 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
BASE 10'X10'X6' TROUGH E.B.J. NOT AS PER 250.122
RSLV 06/02/2015 06/02/2015 08/27/2015