Electrical Application Details for App #: B376410
NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
Premises: 1120 BERGEN STREET BROOKLYN BIN: 3030717     Block: 1220   Lot: 24
   
Application Completed and Certified

Filed: 1120 BERGEN ST Census Tract:   315
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11216 Community Board:   308
DOB Cross Street(s):   NOSTRAND AVENUE,    NEW YORK AVENUE
Status:   C - JOB IS SIGNED OFF 03/10/2014
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   01/11/2014 Job Start Date:   12/23/2013
Last Change:   03/10/2014 Job End Date:   12/24/2013
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     03/04/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009858 Licensee Name: MARTIN RUBIN
Firm: 000421 Firm Name: DEVORAH ELECTRIC CORP.
Firm Phone: 718-258-0605  Firm Address: 1491 CONEY ISLAND AVE. BROOKLYN NY 11230 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $102.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: 1120 BERGEN ST LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  BOILR           
Buildings Total               
Total Units : 10 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/10/2014 Notice: 1 - FIRST NOTICE 02/10/2014
Power Issued: 03/10/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO PLUMBING INSPECTIONS COMPLETED FOR THIS PROPERTY
INSPECTION FOR APPLICATION #: B376410
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/23/2014 01/25/2014 CJH V (30) (5) Y
INSPECTION COMMENTS: MAIN BRAKER NOT 2 POLE
 
(2) 02/06/2014 02/10/2014 CJE V Y (25) (1) Y
INSPECTION COMMENTS: N
 
(3) 03/04/2014 03/10/2014 CLC C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B376410
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
PANEL USED AS RACEWAY 312.8
RSLV 01/23/2014 01/23/2014 02/06/2014
 
002 (999) OTHER
CELLAR #14 CONDUCTOR IN USED AMEND 210.19
RSLV 01/23/2014 02/06/2014 03/04/2014
 
003 (216) LINE AND LOW VOLTAGE OCCUPY THE SAME ENCLOSURE
CELLAR BOILER CONTROLLER 725
RSLV 01/23/2014 02/06/2014 03/04/2014
 
004 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
CELLAR FEEDER BOILER PANEL 215.2 (A) (1)
RSLV 01/23/2014 02/06/2014 03/04/2014
 
005 (999) OTHER
CELLAR BOILER MAIN CIR BRAKER CANT OPEN ALL UNDERGROUNDED 30A BRAKER240.15 LOAD CALCULATION FOR BOILER FEEDER CONDUCTORS 220.4D
RSLV 01/23/2014 02/06/2014 03/04/2014
 
006 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
FEEDER PIP NOT PROPERLY INSTALLED 358.30
RSLV 02/06/2014 02/06/2014 03/04/2014