Query Inspection Results:1-07-22767
Premises: 604 WEST 141 STREET MANHATTAN Job No: 102413933 01
BIN: 1062322    Block: 2088    Lot: 38 Permit Number: 102413933
Licensee: P  000800 Permit Type: ARA
GAS SERVICE  |  COMMENTS

Floor - Apts - Insp Area: 1, 2, 3 - 1C, 2C, 3C -
Work Description: REPLACE 20' OF 3/4" GAS PIPING FROM METER TO GAS RANGE IN APTS 1C,2C,3C DUE TO
GAS LEAKS IN GAS PIPING.GAS CERT. REQ.EXP.9/27/08

Inspector Badge: 2259 Date of Inspection: 10/22/2007 Time Scheduled: 10:06 ACTUAL
Inspection Reference #: 0000564950 Status: INSPECTION CONDUCTED Type: I - INSPECTION
Accela Inspection #:


RESULTS:
FLOOR REF NO SYSTEM COMPONENT TEST / INSPECTION RESULT
001 1722222 0 7 - GAS 7100 - GAS-FIXTURES I71A - GAS SYSTEM FINISH FAIL
002 1748741 0 7 - GAS 7100 - GAS-FIXTURES I71A - GAS SYSTEM FINISH FAIL
003 1748742 0 7 - GAS 7100 - GAS-FIXTURES I71A - GAS SYSTEM FINISH FAIL
003 1722220 0 7 - GAS 7201 - GAS PIPING I72B - GAS PIPING ROUGHING FAIL
001 1748743 0 7 - GAS 7201 - GAS PIPING I72B - GAS PIPING ROUGHING FAIL
002 1748744 0 7 - GAS 7201 - GAS PIPING I72B - GAS PIPING ROUGHING FAIL
002 1722221 0 7 - GAS 7201 - GAS PIPING T72A - GAS PIPING GAS TEST LOW FAIL
003 1748745 0 7 - GAS 7201 - GAS PIPING T72A - GAS PIPING GAS TEST LOW FAIL
001 1748746 0 7 - GAS 7201 - GAS PIPING T72A - GAS PIPING GAS TEST LOW FAIL
(*) Changes to these tests after the initial inspection scheduling may not be reflected on this website.

COMMENTS: TOTAL: 9      

GAS DETAILS - AUTHORIZED FOR THE FOLLOWING END USES: NO AUTHORIZATIONS