Comments for Work Order: 4-09-24582
Premises: 11-24 31 AVENUE QUEENS Job No: 402502760 01
BIN: 4540105    Block: 503    Lot: 7502 Permit Number: 402502760
Licensee: 000362 Permit Type: STANDPIPE

To view plumbing objections, please visit Inspection Ready

CODE FLOOR REF NO SYSTEM TEST / INSPECTION INSPECTION
      DATE
RESOLVING
INSPECTION
RESOLVED
      DATE
NEWOBJ 000 0002823445 0 - ALL I00B - NOT APPLICABLE 01/11/2010 4-09-24582 01/11/2010
Description: FIRE PUMP PRESSURE ON TOP FLOOR 90 PSI.1ST READING 70 PSI WITH PUMP AT 88 PAS, 2ND PETOT READ 68. BOTH PETOT 54 PSI AND 52 PSI WITN 88 PSI AT TOP MANIFOLD
NEWOBJ 000 0002823443 0 - ALL I00B - NOT APPLICABLE 01/11/2010 4-09-24582 04/13/2011
Description: IN RISER DIAGRAM INDICATE 11/4'' PIPING FOR JOCKEY PUMP
NEWOBJ 000 0002823444 0 - ALL I00B - NOT APPLICABLE 01/11/2010 4-09-24582 04/13/2011
Description: AMEND PLANS TO SHOW THE 3 VALVES MANIFOLD ON THE 21ST GLOOR, NOT ON 20
NEWOBJ 000 0002823441 0 - ALL I00B - NOT APPLICABLE 01/11/2010 4-09-24582 04/13/2011
Description: AMEND PLANS AND SCHDL B TO SHOW 20 AND 21ST FLOORS
NEWOBJ 000 0002823442 0 - ALL I00B - NOT APPLICABLE 01/11/2010 4-09-24582 04/13/2011
Description: AMEND PLANS TO SHOW DRIP VALVE AND MANHOLE FOR UNDERGROUND PIPING FOR SIAMESSE