| NEWOBJ | 000 | 0002203855 | 0 - ALL | I00B - NOT APPLICABLE | 09/25/2008 | 4-08-18079 | 09/25/2008 |
| Description: LMP SUBMIT LETTER FOR HANGERS ON FLUE FOR HWH | |||||||
| NEWOBJ | 000 | 0002203846 | 0 - ALL | I00B - NOT APPLICABLE | 09/25/2008 | 4-08-18079 | 12/23/2008 |
| Description: AMEND PLANS TO SHOW LAARS BOILER,AO.SMITH HWH,BTU,MEA | |||||||
| NEWOBJ | 000 | 0002203847 | 0 - ALL | I00B - NOT APPLICABLE | 09/25/2008 | 4-08-18079 | 12/23/2008 |
| Description: NEED HANGER ON FLU PIPING | |||||||
| NEWOBJ | 000 | 0002203848 | 0 - ALL | I00B - NOT APPLICABLE | 09/25/2008 | 4-08-18079 | 12/23/2008 |
| Description: NEED GAS ROUGH ,,& TEST FOUND OPEN END IN CEILING WITH VALVE. | |||||||
| LL17/01 | 001 | 0002203849 | 7 - GAS | T72A - GAS PIPING GAS TEST LOW | 09/25/2008 | 4-08-18079 | 12/23/2008 |
| Description: TEST: 3 PSIG FOR 1/2 HOUR: UP TO 14" WC". OPER. | |||||||
| NEWOBJ | 000 | 0002203850 | 0 - ALL | I00B - NOT APPLICABLE | 09/25/2008 | 4-08-18079 | 12/23/2008 |
| Description: NEED GAS ROUGH IN CELLAR FOR DRYER PIPE NOT COMPLETE. | |||||||
| NEWOBJ | 000 | 0002203851 | 0 - ALL | I00B - NOT APPLICABLE | 09/25/2008 | 4-08-18079 | 12/23/2008 |
| Description: LMP SUBMIT GAS APPLIANCES LETTERS | |||||||
| LL17/01 | 002 | 0002203852 | 7 - GAS | T72A - GAS PIPING GAS TEST LOW | 09/25/2008 | 4-08-18079 | 12/23/2008 |
| Description: TEST: 3 PSIG FOR 1/2 HOUR: UP TO 14" WC". OPER. | |||||||
| LL17/01 | CEL | 0002203853 | 7 - GAS | T72A - GAS PIPING GAS TEST LOW | 09/25/2008 | 4-08-18079 | 12/23/2008 |
| Description: TEST: 3 PSIG FOR 1/2 HOUR: UP TO 14" WC". OPER. | |||||||
| LL17/01 | OSP | 0002203854 | 7 - GAS | T72A - GAS PIPING GAS TEST LOW | 09/25/2008 | 4-08-18079 | 12/23/2008 |
| Description: TEST: 3 PSIG FOR 1/2 HOUR: UP TO 14" WC". OPER. | |||||||