| NYC Department of Buildings | ||
| Comments for Work Order: 3-05-11381 | ||
| Premises: 53 FRONT STREET BROOKLYN | Job No: 301506298 01 | ||
| BIN: 3329418 Block: 36 Lot: 7503 | Permit Number: 301506298 | ||
| Licensee: 000362 | Permit Type: SPRINKLER | ||
| CODE | FLOOR | REF NO | SYSTEM | TEST / INSPECTION | INSPECTION DATE |
RESOLVING INSPECTION |
RESOLVED DATE |
| NEWOBJ | 000 | 0000625580 | 0 - ALL | I00B - NOT APPLICABLE | 07/08/2005 | 3-05-11381 | 07/08/2005 |
| Description: SUBMIT ELECTRICAL LETTER FROM LICENCED ELECTRICIAN WIRED ALL SUPERVISOY DEVICES PER CODE, FA LETTER OF APPROVAL, FP-85 IF HYDR IS SUCESSFUL. | |||||||
| NEWOBJ | 000 | 0000625581 | 0 - ALL | I00B - NOT APPLICABLE | 07/08/2005 | 3-05-11381 | 07/08/2005 |
| Description: IF FA IS EXSISTING, ARCHITECT SHALL SUBMIT LETTER. | |||||||
| NEWOBJ | 000 | 0000625578 | 0 - ALL | I00B - NOT APPLICABLE | 07/08/2005 | 3-05-12080 | 07/15/2005 |
| Description: EXSISTING WATER SERVICE FOR SPRINKLER, PUMP, ALARM VALVE. | |||||||
| NEWOBJ | 000 | 0000625579 | 0 - ALL | I00B - NOT APPLICABLE | 07/08/2005 | 3-05-12080 | 07/15/2005 |
| Description: SUPPLY OF SPARE HEADS, WRENCH NEEDED | |||||||
| NEWOBJ | 000 | 0000625582 | 0 - ALL | I00B - NOT APPLICABLE | 07/08/2005 | 3-05-12080 | 07/15/2005 |
| Description: PLAN SHOWS EXSISTING FIRE DETECTION SYSTEM (FA) | |||||||
| NEWOBJ | 000 | 0000625583 | 0 - ALL | I00B - NOT APPLICABLE | 07/08/2005 | 3-05-12080 | 07/15/2005 |
| Description: NEED STANDPIPE HYDRO, FINISH INSPECTION. | |||||||
| NEWOBJ | 000 | 0000625584 | 0 - ALL | I00B - NOT APPLICABLE | 07/08/2005 | 3-05-12080 | 07/15/2005 |
| Description: EXSISTING COMBINATION SD/SP SYSTEM PER APPROVED PLAN. | |||||||
| DOBOBJ | CEL | 0000625585 | 1 - SPRINKLER | T12A - SP PIPING HYDROSTATIC TEST | 07/08/2005 | 3-05-12080 | 07/15/2005 |
| Description: CANNOT TEST THROUGH SPRINKLER HEAD. | |||||||