| NYC Department of Buildings | ||
| Comments for Work Order: 3-10-04196 | ||
| Premises: 160 FRANKLIN AVENUE BROOKLYN | Job No: 302357606 01 | ||
| BIN: 3322396 Block: 1912 Lot: 36 | Permit Number: 302357606 | ||
| Licensee: 000677 | Permit Type: SPRINKLER | ||
| CODE | FLOOR | REF NO | SYSTEM | TEST / INSPECTION | INSPECTION DATE |
RESOLVING INSPECTION |
RESOLVED DATE |
| NEWOBJ | 000 | 0002923552 | 0 - ALL | I00B - NOT APPLICABLE | 04/09/2010 | 3-10-06286 | 05/17/2010 |
| Description: MODIFY APPLICATION TO SHOW 2 SPRK HEADS ON ROOF | |||||||
| NEWOBJ | 000 | 0002923553 | 0 - ALL | I00B - NOT APPLICABLE | 04/09/2010 | 3-10-06286 | 05/17/2010 |
| Description: ON ROOF- SIGN "INSP. TEST'' REQUIRE ON ACCES DOOR; LANDING HEAD CAP HAS TO BE CHANGED < NO SILICON PERMITTED AROUND >; BOILER ROOM SPRK HEAD REQUIRE CORRECT RATING < BLUE BULB> | |||||||
| NEWOBJ | 000 | 0002923554 | 0 - ALL | I00B - NOT APPLICABLE | 04/09/2010 | 3-10-06286 | 05/17/2010 |
| Description: WALKING CLOSET ON 4TH FL-MIN 18'' FROM SHELF TO HEAD PERMITTED ; MIN - 12 '' FROM LIGHT | |||||||
| NEWOBJ | 000 | 0002923555 | 0 - ALL | I00B - NOT APPLICABLE | 04/09/2010 | 3-10-06286 | 05/17/2010 |
| Description: 3RD FL- CHANGE CAPS < LANDING AND CABINET ROOM>- NO SILICON AROUND PERMITTED | |||||||
| NEWOBJ | 000 | 0002923556 | 0 - ALL | I00B - NOT APPLICABLE | 04/09/2010 | 3-10-06286 | 05/17/2010 |
| Description: MODIFY PLAN TO SHOW SPRK HEAD ON ROOF STAIR LANDING | |||||||
| DOBOBJ | CEL | 0002923557 | 1 - SPRINKLER | I11A - SP SYSTEM FINISH | 04/09/2010 | 3-10-06286 | 05/17/2010 |
| Description: NO COVERED CELL STAIRS LANDING | |||||||
| DOBOBJ | CEL | 0002923558 | 1 - SPRINKLER | I11A - SP SYSTEM FINISH | 04/09/2010 | 3-10-06286 | 05/17/2010 |
| Description: SILICON NOT PERMITTED AROUND SPRK CAPS | |||||||
| DOBOBJ | 001 | 0002923559 | 1 - SPRINKLER | I11A - SP SYSTEM FINISH | 04/09/2010 | 3-10-06286 | 05/17/2010 |
| Description: MISSING COVERAGE BETWEEN DOORS ON 1 ST FL ENTRANCE | |||||||
| DOBOBJ | 001 | 0002923560 | 1 - SPRINKLER | I11A - SP SYSTEM FINISH | 04/09/2010 | 3-10-06286 | 05/17/2010 |
| Description: SILICON NOT PERMITTED AROUND SPRK CAPS | |||||||
| NEWOBJ | 000 | 0002923561 | 0 - ALL | I00B - NOT APPLICABLE | 04/09/2010 | 3-10-06286 | 05/17/2010 |
| Description: ALL RISER CONTROLS VALVES REQUIRE LOCKED BY CHAINS IN OPEN POSITION | |||||||