To view plumbing objections, please visit Inspection Ready

CODE FLOOR REF NO SYSTEM TEST / INSPECTION INSPECTION
      DATE
RESOLVING
INSPECTION
RESOLVED
      DATE
SCHEDB 001 0002739456 7 - GAS I00B - NOT APPLICABLE 11/02/2009 3-09-22069 01/19/2010
Description: MODIFY SCHEDULE B AND PLAN (0) TO AGREE WITH ACTUAL (1) FOR SCHEDULE B GAS FURNACE FOR FLOOR 001
NEWOBJ 000 0002739457 0 - ALL I00B - NOT APPLICABLE 11/02/2009 3-09-22069 01/19/2010
Description: FAI REQUIED FOR GAS METER ROOM IN CELLAR.
SCHEDB CEL 0002739458 3 - WATER & SANITARY I00B - NOT APPLICABLE 11/02/2009 3-09-22069 01/19/2010
Description: MODIFY SCHEDULE B AND PLAN (1) TO AGREE WITH ACTUAL (0) FOR SCHEDULE B LAVATORY (COMMON WASH BASIN) FOR FLOOR CEL
SCHEDB CEL 0002739459 7 - GAS I00B - NOT APPLICABLE 11/02/2009 3-09-22069 01/19/2010
Description: MODIFY SCHEDULE B AND PLAN (1) TO AGREE WITH ACTUAL (0) FOR SCHEDULE B GAS FURNACE FOR FLOOR CEL
NEWOBJ 000 0002739460 0 - ALL I00B - NOT APPLICABLE 11/02/2009 3-09-22069 01/19/2010
Description: 3FT WALL BETWEEN ELECTRIC METERS & GAS METER IN CELLAR.
NEWOBJ 000 0002739461 0 - ALL I00B - NOT APPLICABLE 11/02/2009 3-09-22069 01/19/2010
Description: GT PASSED CEL TO 3 FOR HVAC,H/W,C,D. NO GAS AUTHO UNTILL COMMETS REMOVED & GAS FINISH.
SCHEDB 003 0002739462 7 - GAS I00B - NOT APPLICABLE 11/02/2009 3-09-22069 01/19/2010
Description: MODIFY SCHEDULE B AND PLAN (0) TO AGREE WITH ACTUAL (1) FOR SCHEDULE B GAS FURNACE FOR FLOOR 003
SCHEDB BAS 0002739463 7 - GAS I00B - NOT APPLICABLE 11/02/2009 3-09-22069 01/19/2010
Description: MODIFY SCHEDULE B AND PLAN (1) TO AGREE WITH ACTUAL (0) FOR SCHEDULE B GAS FURNACE FOR FLOOR BAS
SCHEDB ROF 0002739464 7 - GAS I00B - NOT APPLICABLE 11/02/2009 3-09-22069 01/19/2010
Description: MODIFY SCHEDULE B (1) AND PLAN (4) TO AGREE WITH ACTUAL (0) FOR SCHEDULE B GAS FURNACE FOR FLOOR ROF
NEWOBJ 000 0002739465 0 - ALL I00B - NOT APPLICABLE 11/02/2009 3-09-22069 01/19/2010
Description: CELLAR BOILER ROOM REQUIRES FIRERATED DOOR W/OUT VENT.