| NYC Department of Buildings | ||
| Comments for Work Order: 3-12-10757 | ||
| Premises: 778 48 STREET BROOKLYN | Job No: 320373341 01 | ||
| BIN: 3012768 Block: 777 Lot: 36 | Permit Number: 320373341 | ||
| Licensee: 002268 | Permit Type: PLUMBING | ||
| CODE | FLOOR | REF NO | SYSTEM | TEST / INSPECTION | INSPECTION DATE |
RESOLVING INSPECTION |
RESOLVED DATE |
| DOBOBJ | UDG | 0003835644 | 3 - WATER & SANITARY | I32A - W&S PIPING UNDERGROUND | 06/29/2012 | 3-12-11837 | 07/26/2012 |
| Description: UNDERGROUND WASTE PIPE COVER WITH CEMENT/NOT EXPOSED. | |||||||
| DOBOBJ | CEL | 0003835647 | 7 - GAS | I72B - GAS PIPING ROUGHING | 06/29/2012 | 3-12-11837 | 07/26/2012 |
| Description: NEED SLEEVES ON GAS PIPE PASSING THROUGH CEMENT WALL. | |||||||
| NEWOBJ | 000 | 0003835643 | 0 - ALL | I00B - NOT APPLICABLE | 06/29/2012 | 3-12-11837 | 07/26/2012 |
| Description: DO TO GAS PIPE WAS PAINTED PRIOR TO GAS TEST, LMP PREFORMING 90 PSI AT TIME OF INSPECTION. | |||||||
| FGC 107.1.3 | CEL | 0003835648 | 7 - GAS | T72A - GAS PIPING GAS TEST LOW | 06/29/2012 | 3-12-11837 | 07/26/2012 |
| Description: PIPING NOT EXPOSED FOR TEST/INSPECTION | |||||||
| 28-105.12.2 | 001 | 0003835646 | 3 - WATER & SANITARY | I32B - W&S PIPING ROUGHING | 06/29/2012 | 3-12-10757 | 11/12/2013 |
| Description: WORK DOES NOT CONFORM TO APPROVED PLANS | |||||||
| NEWOBJ | 000 | 0003835645 | 0 - ALL | I00B - NOT APPLICABLE | 06/29/2012 | 3-12-10757 | 11/12/2013 |
| Description: 3 INCH VENT LINE REDUCED TO 2 INCH IN 1ST FLR APT IN CEILING. | |||||||