Comments for Work Order: 2-09-07083
Premises: 712 EAST 214 STREET BRONX Job No: 210009578 01
BIN: 2117623    Block: 4661    Lot: 12 Permit Number: 210009578
Licensee: 001568 Permit Type: PLUMBING

To view plumbing objections, please visit Inspection Ready

CODE FLOOR REF NO SYSTEM TEST / INSPECTION INSPECTION
      DATE
RESOLVING
INSPECTION
RESOLVED
      DATE
NEWOBJ 000 0002772712 0 - ALL I00B - NOT APPLICABLE 11/30/2009    
Description: CORRECT GAS RISER DIAGRAM TO SHOW 5 METERS 3 METERS FEEDING BOILERS HOT WATER HEATERS AND STOVES THE OTHER 2 METERS FEEDING HOT WATER HEATERS
SCHEDB 003 0002772713 3 - WATER & SANITARY I00B - NOT APPLICABLE 11/30/2009    
Description: MODIFY SCHEDULE B (1) TO AGREE WITH ACTUAL (0) FOR SCHEDULE B DISHWASHER FOR FLOOR 003
SCHEDB 004 0002772715 3 - WATER & SANITARY I00B - NOT APPLICABLE 11/30/2009    
Description: MODIFY SCHEDULE B (1) TO AGREE WITH ACTUAL (0) FOR SCHEDULE B DISHWASHER FOR FLOOR 004
SCHEDB 002 0002772719 3 - WATER & SANITARY I00B - NOT APPLICABLE 11/30/2009    
Description: MODIFY SCHEDULE B (1) TO AGREE WITH ACTUAL (0) FOR SCHEDULE B DISHWASHER FOR FLOOR 002
NEWOBJ 000 0002772709 0 - ALL I00B - NOT APPLICABLE 11/30/2009 2-09-07383 12/10/2009
Description: GAS METER THAT DID NOT HOLD WAS THE 4TH ONE FROM LEFT TO RIGHT
NEWOBJ 000 0002772710 0 - ALL I00B - NOT APPLICABLE 11/30/2009 2-09-07383 12/10/2009
Description: STILL NEED GAS TEST FOR METER THAT DOES 3RD FLOOR
LL17/01 003 0002772714 7 - GAS T72A - GAS PIPING GAS TEST LOW 11/30/2009 2-09-07383 12/10/2009
Description: TEST: 3 PSIG FOR 1/2 HOUR: UP TO 14" WC". OPER.
NEWOBJ 000 0002772717 0 - ALL I00B - NOT APPLICABLE 11/30/2009 2-09-07383 12/10/2009
Description: NEED TO INSTALL FLOOR DRAIN IN BOILER ROOM
NEWOBJ 000 0002772718 0 - ALL I00B - NOT APPLICABLE 11/30/2009 2-09-07383 12/10/2009
Description: NO GAS AUTH UNTIL FLOOR DRAIN IS INSTALLED AND 3RD FLOOR GAS METER IS INSPECTED
SCHEDB CEL 0002772706 7 - GAS I00B - NOT APPLICABLE 11/30/2009 2-09-07083 11/26/2010
Description: MODIFY SCHEDULE B (3) TO AGREE WITH ACTUAL (5) FOR SCHEDULE B GAS WATER HEATER FOR FLOOR CEL