| CODE | FLOOR | REF NO | SYSTEM | TEST / INSPECTION | INSPECTION DATE |
RESOLVING INSPECTION |
RESOLVED DATE |
| FGC 106.5 | CEL | 0003748090 | 7 - GAS | I71A - GAS SYSTEM FINISH | 04/17/2012 | 2-12-02685 | 05/24/2012 |
| Description: WORK DOES NOT CONFORM TO APPROVED PLANS | |||||||
| NEWOBJ | 000 | 0003748089 | 0 - ALL | I00B - NOT APPLICABLE | 04/17/2012 | 2-12-02685 | 05/24/2012 |
| Description: NO GT,GR FAILED. | |||||||
| FGC 406.4 | CEL | 0003748088 | 7 - GAS | T72A - GAS PIPING GAS TEST LOW | 04/17/2012 | 2-12-02685 | 05/24/2012 |
| Description: VALVE & PIPING: TEST PRESSURE THREE (3 PSIG) MIN 30 MINUTES | |||||||
| NEWOBJ | 000 | 0003748091 | 0 - ALL | I00B - NOT APPLICABLE | 04/17/2012 | 2-12-02685 | 05/24/2012 |
| Description: 3/4" GAS PURGE NOT PERMITTED,1/2" ONLY. | |||||||
| NEWOBJ | 000 | 0003748087 | 0 - ALL | I00B - NOT APPLICABLE | 04/17/2012 | 2-12-02685 | 05/24/2012 |
| Description: LAMPWICK NOT PERMITTED TO BE USE ON PIPE THREADS FOR GAS PIPE. | |||||||
| FGC 106.5 | CEL | 0003748086 | 7 - GAS | I72B - GAS PIPING ROUGHING | 04/17/2012 | 2-12-02685 | 05/24/2012 |
| Description: WORK DOES NOT CONFORM TO APPROVED PLANS | |||||||