| NYC Department of Buildings | ||
| Comments for Work Order: 1-07-15922 | ||
| Premises: 111 MURRAY STREET MANHATTAN | Job No: 104793118 01 | ||
| BIN: 1089698 Block: 142 Lot: 7503 | Permit Number: 104793118 | ||
| Licensee: 000097 | Permit Type: SPRINKLER | ||
| CODE | FLOOR | REF NO | SYSTEM | TEST / INSPECTION | INSPECTION DATE |
RESOLVING INSPECTION |
RESOLVED DATE |
| 27-967 | 008 | 0001639229 | 1 - SPRINKLER | T12A - SP PIPING HYDROSTATIC TEST | 08/03/2007 | 1-07-17796 | 08/13/2007 |
| Description: SPRINKLER SYSTEM NOT PROPERLY TESTED | |||||||
| 27-967 | 010 | 0001639231 | 1 - SPRINKLER | T12A - SP PIPING HYDROSTATIC TEST | 08/03/2007 | 1-07-17796 | 08/13/2007 |
| Description: SPRINKLER SYSTEM NOT PROPERLY TESTED | |||||||
| NEWOBJ | 000 | 0001639233 | 0 - ALL | I00B - NOT APPLICABLE | 08/03/2007 | 1-07-17796 | 08/13/2007 |
| Description: SPRINKLER SYSTEM NEEDS TO BE TESTED WITH CONTROL VALVE PIPING CONNECTED,NOT CAPPED. | |||||||
| 27-967 | 009 | 0001639230 | 1 - SPRINKLER | T12A - SP PIPING HYDROSTATIC TEST | 08/03/2007 | 1-07-15922 | 03/21/2014 |
| Description: SPRINKLER SYSTEM NOT PROPERLY TESTED | |||||||
| NEWOBJ | 000 | 0001639232 | 0 - ALL | I00B - NOT APPLICABLE | 08/03/2007 | 1-07-15922 | 03/21/2014 |
| Description: FINISH PENDING CLARIFICATION OF SIDE WALL SPRINKLER HEADS 16" FROM CEILING ( IN CERTAIN DORM APTS ),IN ORDER TO CLEAR BEAMS OBSTRUCTING THE SPRINKLER HEADS. | |||||||
| NEWOBJ | 000 | 0001639234 | 0 - ALL | I00B - NOT APPLICABLE | 08/03/2007 | 1-07-15922 | 03/21/2014 |
| Description: ALSO NEED PLANS TO HAVE LEGEND SHOWING SPRINKLER TYPE | |||||||