| NYC Department of Buildings | ||
| Comments for Work Order: 1-17-71004 | ||
| Premises: 516 WEST 134 STREET MANHATTAN | Job No: 122430226 01 | ||
| BIN: 1059746 Block: 1987 Lot: 46 | Permit Number: 122430226 | ||
| Licensee: 002334 | Permit Type: PLUMBING | ||
| CODE | FLOOR | REF NO | SYSTEM | TEST / INSPECTION | INSPECTION DATE |
RESOLVING INSPECTION |
RESOLVED DATE |
| 000 | 0010058419 | 11/13/2017 | |||||
| Description: ALL OUTSIDE PIPING MUST BE CORROSION PROTECTED PRIOR TO GAS FINISH | |||||||
| CEL | 0010058420 | 11/13/2017 | |||||
| Description: RISER DIAGRAM SHOWS 2 GAS VENTS ON GAS TRAIN WITH THE STATEMENT "VENTS TO OUTSIDE (AS REQUIRED PER MFG. SPECS)". LMP DID NOT INSTALL THEM AND SAID THEY WERENT NECESSARY. MUST EITHER REMOVE THEM FROM RISER DIAGRAM AND PROVIDE MFGS PAPERW (+) | |||||||