| NYC Department of Buildings | ||
| Comments for Work Order: 1-05-16771 | ||
| Premises: 849 7 AVENUE MANHATTAN | Job No: 104175278 01 | ||
| BIN: 1023388 Block: 1007 Lot: 61 | Permit Number: 104175278 | ||
| Licensee: 008790 | Permit Type: PLUMBING | ||
| CODE | FLOOR | REF NO | SYSTEM | TEST / INSPECTION | INSPECTION DATE |
RESOLVING INSPECTION |
RESOLVED DATE |
| LL17/01 | CEL | 0000677021 | 7 - GAS | T72A - GAS PIPING GAS TEST LOW | 08/18/2005 | 1-05-17717 | 08/31/2005 |
| Description: TEST: 3 PSIG FOR 1/2 HOUR: UP TO 14" WC". OPER. | |||||||
| 27-904 | 001 | 0000677024 | 7 - GAS | I71A - GAS SYSTEM FINISH | 08/18/2005 | 1-05-17717 | 08/31/2005 |
| Description: APPLIANCE(S) NOT READY FOR SERVICE: | |||||||
| 27-201 | 001 | 0000677020 | 7 - GAS | I72B - GAS PIPING ROUGHING | 08/18/2005 | 1-05-16771 | 11/14/2005 |
| Description: WORK DOES NOT CONFORM TO APPROVED PLANS | |||||||
| NEWOBJ | 000 | 0000677022 | 0 - ALL | I00B - NOT APPLICABLE | 08/18/2005 | 1-05-16771 | 11/14/2005 |
| Description: NEED FLOOR PLANS TO SHOW GAS PIPING IN PUBLIC HALLS AND SHOW 2 HOUR RATED FIRE WALLS | |||||||
| NEWOBJ | 000 | 0000677023 | 0 - ALL | I00B - NOT APPLICABLE | 08/18/2005 | 1-05-16771 | 11/14/2005 |
| Description: GAS DISTRIBUTION PIPING HAVE FUTURE TEES ON SEVERAL FLOORS AND FULL SIZE TEES IN BASE OF RISER | |||||||