| Premises: 90 BOWERY MANHATTAN | Job No: 104224787 01 | ||
| BIN: 1003136 Block: 239 Lot: 38 | Permit Number: 104224787 | ||
| Licensee: 000794 | Permit Type: STANDPIPE | ||
| CODE | FLOOR | REF NO | SYSTEM | TEST / INSPECTION | INSPECTION DATE |
RESOLVING INSPECTION |
RESOLVED DATE |
| NEWOBJ | 000 | 0001827534 | 0 - ALL | I00B - NOT APPLICABLE | 12/12/2007 | 1-08-01803 | 01/24/2008 |
| Description: ALSO FLU PIPING FRESH AIR FROM GAS METER ROOM IS PASSING THROUGH PUMP ROOM ALSO NEEDS TO BE REMOVED | |||||||
| NEWOBJ | 000 | 0001827535 | 0 - ALL | I00B - NOT APPLICABLE | 12/12/2007 | 1-07-27646 | 01/30/2008 |
| Description: DATA ERROR PUMP TEST PASSED IN CELLAR SHOULD BE IN SUB-CELLAR | |||||||
| NEWOBJ | 000 | 0001827536 | 0 - ALL | I00B - NOT APPLICABLE | 12/12/2007 | 1-07-27646 | 01/30/2008 |
| Description: FLOOR DRAIN IN PUMP ROOM IS DUMPING INTO A SUMP PUMP IN PUMP ROOM NEED TO VERIFY IF ALLOWED | |||||||
| NEWOBJ | 000 | 0001827537 | 0 - ALL | I00B - NOT APPLICABLE | 12/12/2007 | 1-07-27646 | 01/30/2008 |
| Description: CHURN 105 PSI/ 1 HOSE TOP MOST 90 PSI, PITOT 62/ 2ND HOSE 89 PSI, PITOT 65/ BOTH HOSE 60 PSI, PITOT 46 1ST HOSE/ 46 2ND HOSE | |||||||
| NEWOBJ | 000 | 0001827538 | 0 - ALL | I00B - NOT APPLICABLE | 12/12/2007 | 1-07-27646 | 01/30/2008 |
| Description: NEED A LETTER FROM RA OR PE EXPLAINING 2" AUXILIARY SERVICE TIED INTO 6" FIRE SERVICE ALSO ON PLANS | |||||||
| NEWOBJ | 000 | 0001827539 | 0 - ALL | I00B - NOT APPLICABLE | 12/12/2007 | 1-07-27646 | 01/30/2008 |
| Description: PLANS NEED TO SHOW PUMP INFORMATION/ PUMP INSTALLED IS A AUTOMATIC 500 GPM AC FIRE PUMP SERIAL # 07-048096-04-01 /QKC912 | |||||||
| NEWOBJ | 000 | 0001827540 | 0 - ALL | I00B - NOT APPLICABLE | 12/12/2007 | 1-07-27646 | 01/30/2008 |
| Description: NOTE AS PER PLANS AND AS BUILT A 2" SERVICE OFF DOMESTIC IS TIED INTO 6" THE FIRE SERVICE FEEDING FIRE PUMP. PUMP WAS TESTED WITH 6" SERVICE ONLY/ AS PER PUMP REP 2" SERVICE IN NOT A SUFFICIENT WATER SUPPLY FOR PUMP TEST | |||||||
| NEWOBJ | 000 | 0001827541 | 0 - ALL | I00B - NOT APPLICABLE | 12/12/2007 | 1-07-27646 | 01/30/2008 |
| Description: THERE'S A WINDOW TO THE FIRE PUMP ROOM WHICH LEADS TO OUTSIDE, IF LEFT OPEN COULD EXPOSE FIRE PUMP TO OUTSIDE WEATHER NEEDS TO BE REMOVED PUMP ROOM MUST PROPERLY HEATED | |||||||
| REVWSO | 000 | 0001954093 | 2 - STANDPIPE | I21A - SD SYSTEM FINISH SD | 03/18/2008 | 1-07-27646 | 03/18/2008 |
| Description: OK | |||||||