BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z144575
NO RECORDS FOUND
Premises: 227 AUDUBON AVENUE MANHATTAN BIN: 1063182     Block: 2132   Lot: 18
   
Application Completed and Certified

Filed: 227 AUDUBON AV Census Tract:   261 Health Area:  0400
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10033 Community Board:   112
DOB Cross Street(s):   WEST 176 STREET,    WEST 177 STREET
Status:   C - JOB IS SIGNED OFF 03/17/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/03/2014 5:22 PM
Application Entered:   06/03/2014 Job Start Date:   06/03/2014
Last Change:   03/17/2015 Job End Date:   11/30/2014
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     02/27/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 011008 Licensee Name: LAURENCE H ROBIN
Firm: 001260 Firm Name: ROBIN ELECTRICAL CO., INC
Firm Phone: 718-292-6535  Firm Address: 437 EAST 165TH ST. B704 BRONX NY 10456 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $100.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SUSAN EDELSTEIN
Owner Business Name: AUDUBON REALTY LLC
Authorized Representative:  EDWIN ALGARIN
Relationship To Owner:   BUILDING MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  HOUSE COMBO MAIN/DISTRIBU
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  1/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/03/2014 Notice:  
Power Issued: 06/03/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  TO ELIMINATE SHUNT FROM STREET.

 
Inspection Details
 

*NO RECORDS FOUND
INSPECTION FOR APPLICATION #: Z144575
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/27/2015 03/06/2015 BMP C E (35) (0) Y
INSPECTION COMMENTS: NONE




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order