Electrical Application Details for App #: Z157454
NO RECORDS FOUND
Premises: 729 8 AVENUE MANHATTAN BIN: 1081653     Block: 1036   Lot: 36
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 729 8TH AV Census Tract:   121 Health Area:  4500
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   G
NEW YORK, NY 10036 Community Board:   104
DOB Cross Street(s):   WEST 45 STREET,    WEST 46 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/13/2016 2:30 PM
Application Entered:   10/13/2016 Job Start Date:   10/14/2016
Last Change:   08/22/2025 Job End Date:   10/20/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     10/04/2022      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 011377 Licensee Name: BENJAMIN BELOT
Firm: 003843 Firm Name: LEADER ELECTRIC CO., INC
Firm Phone: 212-665-0606  Firm Address: 857 SOUTHERN BLVD BRONX NY 10459 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
T - TEMPORARY LIGHT & POWER
Total Fee:  $85.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   COMMERCIAL/OFFICE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PHIL CAPORASO
Owner Business Name: CHDC
Authorized Representative:  NEIL FAIREY
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4 # 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  BAS                       
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 10/13/2016 Notice: 1 - FIRST NOTICE 02/16/2022
Power Issued: 10/13/2016 Response:  

Follow-Up:
Contractor's Comments:  N/A

 
Inspection Details
 

*NO RECORDS FOUND
INSPECTION FOR APPLICATION #: Z157454
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/04/2017 08/07/2017 MLF N (15) (0) Y
INSPECTION COMMENTS: CONTRACTOR WILL RESCHEDULE " RUNNING LATE"
 
(2) 08/16/2017 08/16/2017 MQY V (34) (3)
INSPECTION COMMENTS: ISSUED OBJECTIONS. CONTRACTOR SAID LEADER ELECTRIC INSTALLED THE NEW SERVICE SWITCH INSIDE THE RESTAURANT. CONTRACTOR HAS TO AMEND THIS APPLICATION TO INCLUDE SERVICE SWITCH AND FEEDERS. FULL INSPECTION NEEDED
 
(3) 12/12/2017 12/12/2017 TOR H X (30) (0) Y
INSPECTION COMMENTS: FAIL
 
(4) 02/26/2018 02/27/2018 STP N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT SHOW UP.
 
(5) 09/30/2019 10/01/2019 VTC V Y (50) (3)
INSPECTION COMMENTS: FAIL
 
(6) 01/27/2022 01/27/2022 AGF N (35) (0) Y
INSPECTION COMMENTS: NO SHOW ... INCOMPLETE INSPECTION , CALLS MADE TO OFFICE , COULD NOT GET IN TOUCH WITH ANYONE .
 
(7) 02/15/2022 02/16/2022 DWB V R (66) (3)
INSPECTION COMMENTS: INSPECTION COMPLETE,PAA REQUIRED, OBJECTION ISSUED. SEE ATTACHMENT LETTER OF APPROVAL OF SERVICES SWITCHES.
 
(8) 10/04/2022 10/04/2022 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000031727

OBJECTION FOR APPLICATION #: Z157454
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) SERVICE SWITCH NOT GROUPED (230.40)
RSLV 08/16/2017 08/16/2017 02/15/2022
 
002 (999) OTHER
(BASEMENT)LOAD SIDE OF SERVICE SWITCH NO EGC IN THE GREENFIELD FEEDERS (PANELSNOT GROUNDED)(250.118)
RSLV 08/16/2017 08/16/2017 09/30/2019
 
003 (999) OTHER
(BASEMENT) SERVICE SWITCH NOT GROUNDED OR BONDED AS PER ARTICLE 250)
RSLV 08/16/2017 08/16/2017 09/30/2019
 
004 (133) NO GROUND ROD: BASEMENT OR OUTSIDE
(BASEMENT) SUPPLEMENTAL GROUND NOT PROVIDED
RSLV 09/30/2019 09/30/2019 02/15/2022
 
005 (999) OTHER
(BASEMENT) KO SEALS MISSING IN TROUGH 110.12
RSLV 09/30/2019 09/30/2019 02/15/2022
 
006 (999) OTHER
(BASEMENT) GREENFIELD NOT PROPERLY SUPPORTED 348.30
RSLV 09/30/2019 09/30/2019 02/15/2022
 
007 (999) OTHER
(ALL FLOORS)PAA REQUIRED, CONTRACTOR NEED TO ADD, SERVICES SWITCHES, 1-201 TO600 AMP, TOTAL 1 INSTALLED,- FEEDERS, 1 SET OVER 250 MCM, TOTAL 2SET INSTALLED. SEE COMMENT.
OPEN 02/15/2022 02/15/2022
 
008 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT)110.16, ARC FLASH LABEL NOT PROVIDED AT NEW ELECTRICAL EQUIPINSTALLED
OPEN 02/15/2022 02/15/2022
 
009 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) SERVICE DISCONNECTS MUST BE IDENTIFIED AS SUCH 230.70(B)
RSLV 02/15/2022 02/15/2022 10/04/2022