BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B400969
NO RECORDS FOUND
Premises: 123 HENRY STREET BROOKLYN BIN: 3001892     Block: 237   Lot: 33
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 123 HENRY ST Census Tract:   5.02 Health Area:  2300
APT. 2D Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   CLARK STREET,    LOVE LANE
Status:   C - JOB IS SIGNED OFF 08/17/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/14/2015 9:18 PM
Application Entered:   09/14/2015 Job Start Date:   09/14/2015
Last Change:   08/17/2016 Job End Date:   09/14/2016
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     07/05/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011522 Licensee Name: FELIX ALEXIS
Firm: 002994 Firm Name: F & L GENERAL ELEC. CORP
Firm Phone: 718-527-1150  Firm Address: 1126 EAST 37TH STREET BROOKLYN NY 11210 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARY ANN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2D                   
Buildings Total                     
Total Units : 9 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/09/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

*NO RECORDS FOUND
INSPECTION FOR APPLICATION #: B400969
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/05/2016 05/09/2016 CCH V (90) (5)
INSPECTION COMMENTS: JOB FAIL
 
(2) 07/05/2016 07/06/2016 CJH C R (20) (0)
INSPECTION COMMENTS: OBJECTION REMOVED

OBJECTION FOR APPLICATION #: B400969
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 002) 30 AMP BREAKER TRIPPING
RSLV 05/05/2016 05/05/2016 07/05/2016
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 002) APT
RSLV 05/05/2016 05/05/2016 07/05/2016
 
003 (999) OTHER
(FLOOR: 002) CT +LIGHTS SAME CIRCUIT 210.52
RSLV 05/05/2016 05/05/2016 07/05/2016
 
004 (999) OTHER
(FLOOR: 002) ALL OUTLETS NOT TAMPER PROOF 406.11
RSLV 05/05/2016 05/05/2016 07/05/2016
 
005 (999) OTHER
(FLOOR: 002) MC CABLE BOXES NOT BONDED 250.146
RSLV 05/05/2016 05/05/2016 07/05/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back