BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Electrical Applications  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Y167118
NO RECORDS FOUND
Premises: 931 EAST 163 STREET BRONX BIN: 2005456     Block: 2703   Lot: 25
   
Application Completed and Certified

Filed: 935 E 163 ST Census Tract:   87 Health Area:  3700
ROOF Admin Area:   Y - BRONX Inspection Area:   C
BRONX, NY 10459 Community Board:   202
DOB Cross Street(s):   INTERVALE AVENUE,    KELLY STREET
Status:   C - JOB IS SIGNED OFF 01/12/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/15/2014 8:44 PM
Application Entered:   01/15/2014 Job Start Date:   01/16/2014
Last Change:   01/12/2015 Job End Date:   12/30/2014
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     09/18/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011316 Licensee Name: RALPH J RUSSO
Firm: 002733 Firm Name: RJ RUSSO ELECTRIC CO.
Firm Phone: 718-423-4742  Firm Address: 45-57 BELL BLVD BAYSIDE NY 11361 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
E - SUSTAINABLE ENERGY - SOLAR
Total Fee:  $252.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: E 163RD LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1-150 AMPS
B. 101 Up to 200 AMPS  1  1-200AMP SER SW
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  2-4#6 WIRES
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 SET-4 #2/0 WIRES
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1-100 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                      153 
ROF              212  53         
Buildings Total              53          153 
Total Units : 206 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/04/2014 Notice: 1 - FIRST NOTICE 08/21/2014
Power Issued: 10/04/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SOLAR INSTALL,212 SOLAR PANELS 250 WATTS EACH, TOTAL 53,000WATTS DC.2 INVERTERS 6 ARRAYS ,1 TRANSFORMER 112.5KW,1 AC DISCONNECT 150 AMPS,1 PANEL 100 AMPS.

 
Inspection Details
 

*NO RECORDS FOUND
INSPECTION FOR APPLICATION #: Y167118
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/14/2014 08/21/2014 GYM A (50) (7) Y
INSPECTION COMMENTS: ISSUE OBJECTIONS TO CONTRACTOR
 
(2) 09/18/2014 10/04/2014 GYM C R E (75) (0) Y
INSPECTION COMMENTS: 1-NEW 200AMP SER SW

OBJECTION FOR APPLICATION #: Y167118
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
NO GROUND ELECTRODE PROVIDED 250.64
RSLV 08/14/2014 08/14/2014 09/18/2014
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BSMT THROUGHOUT
RSLV 08/14/2014 08/14/2014 09/18/2014
 
003 (999) OTHER
NO GROUND CONNECTION AT WATER MAIN WITHIN 5FT
RSLV 08/14/2014 08/14/2014 09/18/2014
 
004 (999) OTHER
NO PHOTOVOLTAIC ELECTRICAL WIRING DIAGRAM PROVIDED 690.1
RSLV 08/14/2014 08/14/2014 09/18/2014
 
005 (999) OTHER
NO BONDING JUMPER AT 200AMP SER SW NEUT. 250.28
RSLV 08/14/2014 08/14/2014 09/18/2014
 
006 (999) OTHER
LABELS FOR HIGH VOLTAGE NOT PROVIDED 408.3
RSLV 08/14/2014 08/14/2014 09/18/2014
 
007 (999) OTHER
200 AMP SER. CONDUIT NOT BONDED 250.92
RSLV 08/14/2014 08/14/2014 09/18/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Electrical Applications  |  Back