BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B354658
NO RECORDS FOUND
Premises: 255 LIVINGSTON STREET BROOKLYN BIN: 3000455     Block: 160   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 255 LIVINGSTON ST Census Tract:   37 Health Area:  2400
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11217 Community Board:   302
DOB Cross Street(s):   BOND STREET,    HANOVER PLACE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/02/2012 7:22 PM
Application Entered:   10/02/2012 Job Start Date:   10/05/2012
Last Change:   08/22/2025 Job End Date:   10/30/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     10/24/2012      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 011824 Licensee Name: COSIMO C CURCIO
Firm: 003431 Firm Name: LCJ ELEC'L CONTR'S INC
Firm Phone: 718-251-3334  Firm Address: 1786 E 49TH STREET BROOKLYN NY 11234 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $670.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (4  Stores, 3 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SHAMASH SOLEYMAN
Owner Business Name: 255 LIVINGSTON REALTY LLC
Authorized Representative:  SHAMASH SOLEYMAN
Relationship To Owner:   SELF


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  5  
B. 101 Up to 200 AMPS  3  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 7 #10-Wire 0
Existing Meters 7 + New Meters 7 - Removed Meters 7 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 10/02/2012 Notice: 1 - FIRST NOTICE 10/31/2012
Power Issued: 10/02/2012 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

*NO RECORDS FOUND
INSPECTION FOR APPLICATION #: B354658
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/24/2012 10/31/2012 DEX A E (60) (3) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: B354658
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
BSMT MTES NOT ISOLATION KIT FOR MTES AFTER 200AMP SEVICE SW
OPEN 10/24/2012 10/24/2012
 
002 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
BSMT 200AMP SERV SW NEUTRAL NOT BONDED TO ENCLRE
OPEN 10/24/2012 10/24/2012
 
003 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
BUG LUG MORE THAN 2 WIRES FOR GRD TO WATERMAIN
OPEN 10/24/2012 10/24/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.