Electrical Application Details for App #: M350061
NO RECORDS FOUND
Premises: 318 EAST 11 STREET MANHATTAN BIN: 1006440     Block: 452   Lot: 17
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 318 E 11 ST Census Tract:   40 Health Area:  6200
BASEMENT/1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/06/2014 9:40 AM
Application Entered:   02/06/2014 Job Start Date:   02/06/2014
Last Change:   08/22/2025 Job End Date:   07/06/2014
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     03/13/2014      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011964 Licensee Name: GWENDOLYN REEDY
Firm: 003626 Firm Name: NIVEK ELEC'L CONTR'G INC
Firm Phone: 212-423-9970  Firm Address: 301 EAST 119TH STREET NEW YORK NY 10035 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $90.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DOMINICK LIO
Owner Business Name: 1350 AOA RESTAURANT CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3-#3 AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  12/24 CKT, MAIN LUG 100A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    23               
001    23  10             
Buildings Total 46  19  12  14                
Total Units : 92 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 03/20/2014
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  GENERAL WIRING. NO SERVICE WORK

 
Inspection Details
 

*NO RECORDS FOUND
INSPECTION FOR APPLICATION #: M350061
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/13/2014 03/20/2014 EDB V (40) (8) Y
INSPECTION COMMENTS: JOB NOT FINISH

OBJECTION FOR APPLICATION #: M350061
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
1 FL: MISSING RECEPTICAL. 210.52
OPEN 03/13/2014 03/13/2014
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
T-OUT: OUTLET BOX(S) MISSING COVERS, 314.25
OPEN 03/13/2014 03/13/2014
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
PANEL: AFCI NOT PROVIDED. 210.12
OPEN 03/13/2014 03/13/2014
 
004 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
T-OUT: OPEN WIRING. AMD. 110.2A
OPEN 03/13/2014 03/13/2014
 
005 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
T-OUT: LIGHT FIXTURE NOT BONDED/GND. 250.4
OPEN 03/13/2014 03/13/2014
 
006 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BSMT: AC CABLE NOT PROPERLY SECURED. 348.30
OPEN 03/13/2014 03/13/2014
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
OUTDOOR: NO GFCI PROVIDED (BACK YARD). 210.8
OPEN 03/13/2014 03/13/2014
 
008 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
BSMT: NO WORKING SPACE IN FRONT OF ELECT. EQUIPMENT. 110.26