BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z125243
Premises: 2381 FREDERICK DOUGLASS BOULEVARD MANHATTAN BIN: 1089108     Block: 1954   Lot: 36
   
Application Completed and Certified

Filed: 300 W 128 ST Census Tract:   213.02 Health Area:  8520
300 WEST 128TH STREET Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10027 Community Board:   110
Special Place Name:   BALTON
Related Job Number:    110469298
DOB Cross Street(s):   FREDERICK DOUGLASS BOULEVARD,    ST NICHOLAS AVENUE
Status:   C - JOB IS SIGNED OFF 07/15/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/24/2010 9:56 AM
Application Entered:   03/24/2010 Job Start Date:   03/26/2010
Last Change:   07/15/2011 Job End Date:   08/30/2010
Appointment Status:   
Last Inspection By:   BEST, J       On     06/30/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010552 Licensee Name: JOSEPH BRAMAN
Firm: 004092 Firm Name: TK ELEVATOR CORPORATION
Firm Phone: 212-947-8800  Firm Address: 519 8TH AVENUE, 6TH FL NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   V1-VACANT LAND
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TIMOTHY JOSEPH
Owner Business Name: NYC HPD
Authorized Representative:  TIMOTHY JOSEPH
Relationship To Owner:   OWNER'S REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/15/2011 Notice: 1 - FIRST NOTICE 03/15/2011
Power Issued: 03/15/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z125243
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/11/2011 03/15/2011 CLC V E (108) (2) Y
INSPECTION COMMENTS: TWO ELEVATORS INSTALLED AT THIS ADDRESS.
 
(2) 03/11/2011 03/15/2011 CLC A R (45) (2) Y
INSPECTION COMMENTS: *TWO ELEVATORS INSTALLED AT THIS ADDRESS* SEE VIOLATION DETAILS
 
(3) 06/30/2011 07/12/2011 JSB C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: Z125243
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (186) 125V, 15/20AMP RECEPTICAL IN MACHINE AREA NOT GFCI
ROOF MOTOR RM GFCI NOT PROVIDED
RSLV 03/11/2011 03/11/2011 03/11/2011
 
002 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
ROOF MOTOR RM CAR LITE DISCONNECTS NEUTRALS BONDED
RSLV 03/11/2011 03/11/2011 03/11/2011
 
003 (999) OTHER
ROOF: MOTOR ROOM G.F.C.I.NOT PROVIDED..... - 620.85
RSLV 03/11/2011 03/11/2011 06/30/2011
 
004 (999) OTHER
ROOF: MOTOR ROOM CAR LIGHT DISCONNECTS NEUTRALS BONDED250.24(A)(5)
RSLV 03/11/2011 03/11/2011 06/30/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order