Electrical Application Details for App #: Z164018
Premises: 1 WEST 72 STREET MANHATTAN BIN: 1028637     Block: 1125   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1 W 72 ST Census Tract:   157
MAIN ELECTRICAL ROOM Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10023 Community Board:   107
DOB Cross Street(s):   CENTRAL PARK EXIT WEST 72 ST,    COLUMBUS AVENUE
Status:   C - JOB IS SIGNED OFF 08/02/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/07/2017 Job Start Date:   11/27/2017
Last Change:   08/02/2018 Job End Date:   11/27/2018
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     08/02/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010144 Licensee Name: JOHN IZZO
Firm: 002205 Firm Name: RESPONSE ELECTRIC INC.
Firm Phone: 718-599-9753  Firm Address: 36 FROST STREET BROOKLYN NY 11211 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $1,585.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54909     Submittal #: 17A0714  
Owner / Occup:
Owner Business Name: THE DAKOTA INC. C/O DOUGL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  18  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  13  SETS 600 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  4  2-800AMP, 2-2000AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/16/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z164018
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/21/2018 05/21/2018 EDB V (165) (6)
INSPECTION COMMENTS: NO ACCESS TO VERTICAL RISER PULL BOX. SEE ATTACHMENT AND DRAWING.
 
(2) 07/16/2018 07/16/2018 DNM V Y (71) (1)
INSPECTION COMMENTS: PANIC BAR ON DOORS, NEED TO BE INSTALLED AS PER ADVISORY BOARD DRAWINGS. OBJECTION WAS MADE CERTIFIABLE
 
(3) 07/23/2018 07/23/2018 TUR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000011225
 
(4) 08/02/2018 08/02/2018 TSO C R (2) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: Z164018
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)INSTALLATION NOT PER DRAWING AM. 110.2
RSLV 05/21/2018 05/21/2018 08/02/2018
 
002 (325) ELECTRICAL CLOSETS SHALL NOT BE USED FOR OTHER PURPOSES
(CELLAR) EL. ROOM USE FOR STORAGE AM. 110.25
RSLV 05/21/2018 05/21/2018 07/16/2018
 
003 (326) EMT IS NOT INSTALLED PER ART 358
(CELLAR) EMT NOT PROPERLY SECURED 358.30
RSLV 05/21/2018 05/21/2018 07/16/2018
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) BUSBAR AMPERE DENSITY NOT PER AM. 230.42
RSLV 05/21/2018 05/21/2018 07/16/2018
 
005 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(ROOF)NO RECEPTACLE WITHIN 25' FROM A/C UNIT 210.63
RSLV 05/21/2018 05/21/2018 07/16/2018
 
006 (999) OTHER
(ROOF)ROOF PANEL : REDUCTION OF NEUTRAL NOT PER ART. 220.61
RSLV 05/21/2018 05/21/2018 07/16/2018
 
007 (999) OTHER
(BASEMENT)PANIC BAR NEEDS TO BE INSTALLED ON DOORS AS PER ADVISORY BOARDDRAWINGS. 110.2
RSLV 07/16/2018 07/16/2018 07/23/2018