BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z163967
Premises: 602 WEST 112 STREET MANHATTAN BIN: 1057331     Block: 1894   Lot: 56
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 610 W 112TH ST Census Tract:   199 Health Area:  2310
CELLAR & 10TH FLOOR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   C
NEW YORK, NY 10025 Community Board:   109
Special Place Name:   BANK STREET SCHOOL EMR UPGRADE
DOB Cross Street(s):   BROADWAY,    RIVERSIDE DRIVE
Status:   C - JOB IS SIGNED OFF 11/05/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/01/2017 2:18 PM
Application Entered:   12/01/2017 Job Start Date:   12/20/2017
Last Change:   11/05/2018 Job End Date:   03/15/2018
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     11/05/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011480 Licensee Name: GREGORY J CARDILLO
Firm: 001965 Firm Name: NEAD ELECTRIC INC.
Firm Phone: 212-764-2752  Firm Address: 530 WEST 50TH STREET NEW YORK NY 10019 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $43.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JUSTIN TYACK
Owner Business Name: BANK STREET COLLEGE OF ED
Authorized Representative:  JUSTIN TYACK
Relationship To Owner:   COO


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                 
010                 
Buildings Total                 
Total Units : 24 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/02/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z163967
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/19/2018 10/19/2018 CLC V (58) (2)
INSPECTION COMMENTS: INSPECTION FAIL, THE ELEVATOR COMPANY MUST FILE AN ELECTRICAL APPLICATION FOR CAR 2 THERE'S NO APPLICATION COVERING THE ELEVATOR CONTROLLER, MOTOR WIRING TOP OF CAR LIGHT AND GFCI CAR 2
 
(2) 11/01/2018 11/02/2018 TSO V R (1) (1)
INSPECTION COMMENTS: OBJ WRITTEN IN ERROR
 
(3) 11/05/2018 11/05/2018 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000017436

OBJECTION FOR APPLICATION #: Z163967
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 020) ELEVATOR DISCONN SWS KO MISSING
RSLV 10/19/2018 10/19/2018 11/01/2018
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF) ELEVATOR DISCONNECT SWS #2 FUSED AT 150AMP
RSLV 10/19/2018 10/19/2018 11/01/2018
 
003 (999) OTHER
(BASEMENT) KO SEAL MISSING
RSLV 11/01/2018 11/01/2018 11/05/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back