Electrical Application Details for App #: Z163508
Premises: 209 WEST 101 STREET MANHATTAN BIN: 1056506     Block: 1873   Lot: 24
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 211 W 101ST ST. Census Tract:   187 Health Area:  3110
CELLAR Admin Area:   Z - UPPER MANHATTAN Inspection Area:   D
NEW YORK, NY 10025 Community Board:   107
DOB Cross Street(s):   AMSTERDAM AVENUE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 12/01/2022
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/01/2017 12:31 PM
Application Entered:   11/01/2017 Job Start Date:   11/01/2017
Last Change:   12/01/2022 Job End Date:   11/01/2018
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     11/29/2022      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009113 Licensee Name: MARTIN WEINSTEIN
Firm: 000796 Firm Name: JOSEPH WEINSTEIN ELECTRIC
Firm Phone: 718-843-5555  Firm Address: 94-24 88TH STREET CORP OZONE PARK NY 11416 

Removal of ECB Violation(s): 35290703M   35290705X   35290657K   35290704Y     
Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $52.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: FRANT HOTEL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    12    12             
CEL  SUPER  10               
Buildings Total 17  17    17                
Total Units : 58 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/22/2022
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z163508
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/22/2022 11/22/2022 ASK V (42) (3)
INSPECTION COMMENTS: FAIL, INSPECTION COMPLETE, OBJECTION ISSUED.
 
(2) 11/29/2022 11/29/2022 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000038536
 
(3) 11/29/2022 11/29/2022 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000038538
 
(4) 11/29/2022 11/29/2022 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000038543

OBJECTION FOR APPLICATION #: Z163508
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (143) LUMINAIRES NOT PROPERLY SUPPORTED/SECURED
(CELLAR) LIGHTS SUPPORTED WITH EMT ART 358.12
RSLV 11/22/2022 11/22/2022 11/29/2022
 
002 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(CELLAR)RECEPTACLE NOT PROPERLY GROUNDED/BONDED (CELLAR) ART 250.146
RSLV 11/22/2022 11/22/2022 11/29/2022
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(CELLAR) EMT CONDUIT NOT PROPERLY SUPPORTED
RSLV 11/22/2022 11/22/2022 11/29/2022