BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z163460
Premises: 3853 10 AVENUE MANHATTAN BIN: 1064508     Block: 2203   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 3853 10 AV Census Tract:   299 Health Area:  0110
APT 4D Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10034 Community Board:   112
DOB Cross Street(s):   IRT-1-BROADWAY/7 AVENUE LINE,    WEST 207 STREET
Status:   C - JOB IS SIGNED OFF 04/13/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/30/2017 2:17 PM
Application Entered:   10/30/2017 Job Start Date:   10/30/2017
Last Change:   04/13/2018 Job End Date:   11/30/2017
Appointment Status:   
Last Inspection By:   MICHAEL QUERY       On     02/20/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011008 Licensee Name: LAURENCE H ROBIN
Firm: 001260 Firm Name: ROBIN ELECTRICAL CO., INC
Firm Phone: 718-292-6535  Firm Address: 437 EAST 165TH ST. B704 BRONX NY 10456 

Removal of ECB Violation(s): 35201971L              
Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (3  Stores, 22 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GEORGE HUANG
Owner Business Name: 449 WEST 206TH STREET HE
Authorized Representative:  TONY HUANG
Relationship To Owner:   BROTHER/MEMBER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  APT PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  4D    10                   
Buildings Total   10                      
Total Units : 10 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/01/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPAIR WIRING DONE BY OTHERS, REPLACE ALL RECEPTACLES, NEW PANEL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z163460
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/30/2017 12/01/2017 MQY V (71) (4)
INSPECTION COMMENTS: NEEDS TO FILE EVERYTHING THAT IS ON THE ECB VIOLATION. ISSUED OBJECTIONS
 
(2) 01/05/2018 01/08/2018 GYM N (20) (0) Y
INSPECTION COMMENTS: TENANT NOT HOME.
 
(3) 01/26/2018 01/29/2018 GYM N (35) (0) Y
INSPECTION COMMENTS: NO SHOW.
 
(4) 02/20/2018 02/21/2018 MQY C R (49) (0)
INSPECTION COMMENTS: Z163974 FOR HALLWAYS

OBJECTION FOR APPLICATION #: Z163460
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 004) ONLY 1 CIRCUIT PROVIDED FOR COUNTERTOP KITCHEN (210.52)
RSLV 11/30/2017 11/30/2017 02/20/2018
 
002 (999) OTHER
(FLOOR: 004)KITCHEN COUNTER CIRCUIT SHARED WITH LIVING ROOM TELEVISION CIRCUIT(210.52
RSLV 11/30/2017 11/30/2017 02/20/2018
 
003 (999) OTHER
(FLOOR: 004) NO PANEL SCHEDULE PROVIDED FOR NEW PANEL
RSLV 11/30/2017 11/30/2017 02/20/2018
 
004 (999) OTHER
(FLOOR: 004) COUNTERTOP RECEPTACLE NEED TO BE GFCI PROETCTED (210.8)
RSLV 11/30/2017 11/30/2017 02/20/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order