Premises: 2 RIVERSIDE BOULEVARD MANHATTAN BIN: 1089741     Block: 1171   Lot: 155
   

DOB NOW: Inspections


Filed: 10 RIVERSIDE BLVD Census Tract:   151 Health Area:  3900
SUBCELLAR, CELLAR, 1-39 & ROOF Admin Area:   Z - UPPER MANHATTAN Inspection Area:   E
NEW YORK, NY 10069 Community Board:   107
Special Place Name:   RIVERSIDE CENTER BUILDING 3
Related Job Number:    121192976
DOB Cross Street(s):   WEST 59 STREET,    WEST 61 STREET
Status:   K - CLOSED/CANCELLED 11/17/2021
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/18/2017 3:12 PM
Application Entered:   10/18/2017 Job Start Date:   10/18/2017
Last Change:   11/17/2021 Job End Date:   04/01/2019
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     11/16/2021      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011289 Licensee Name: PETER BORDUCCI
Firm: 002860 Firm Name: SOLAR ELEC. SYSTEMS, INC.
Firm Phone: 718-824-7000  Firm Address: 1402 BLONDELL AVENUE BRONX NY 10461 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121192976
Building Used As:   Z - Commercial/Residential (36  Stores, 288 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN GAGNIER
Owner Business Name: RCB 3 NOMINEE LLC,A DELAW
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  288  273-2/0, 14-3/0, 1-250
D. Over 250 MCM  46  14-350, 4-3/0, 28-500
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  288  273-125A, 14-150A, 1-200A
C. 3 Phase Up to 225 AMPS  14  12-200A, 2-175A
D. 3 Phase Over 225 AMPS  10  7-800A, 3-400A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  7  3-30HP, 4-40HP
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SUB    72  55    12        750 
CEL    65  49    14        30 
001    110  68    24           
002    112  120    37           
003    138  140    38    12         
004    138  140    38    12         
005    138  140    38    12         
006    138  140    38    12         
007    138  140    38    12         
008    138  140    38    12         
009    138  140    38    12         
010    138  140    38    12         
011    138  140    38    12         
012    138  140    38    12         
013    138  140    38    12         
014    114  128    30    12         
015    114  128    30    12         
016    114  128    30    12         
017    114  128    30    12         
018    114  128    30    12         
019    114  128    30    12         
020    114  128    30    12         
021    114  128    30    12         
022    114  128    30    12         
023    114  128    30    12         
024    114  128    30    12         
025    96  102    26    12         
026    96  102    26    12         
027    96  102    26    12         
028    96  102    26    12         
029    96  102    26    12         
030    96  102    26    12         
031    80  91    23    12         
032    80  91    23    12         
033    80  91    23    12         
034    80  91    23    12         
035    80  91    23    12         
036    80  91    23    12         
037    43  27    12           
038    43  27    12           
039    43  27    12           
ROF    15  12              140 
Buildings Total 4331  4491    1170       78        920 
Total Units : 10996 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/24/2021
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  PERMANENT ELECTRICAL WORK - BRANCH LIGHTING AND POWER WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z163297
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/22/2021 05/24/2021 ASK V (240) (16)
INSPECTION COMMENTS: FAIL. INSPECTION IN COMPLETED. ELEVATORS NO INSPECTED ,NO ELEVATOR COMPANY ON SITE OBJECTION ISSUED. ATOI GIACOMO MARCHESE.
 
(2) 11/16/2021 11/17/2021 ASK K R (10) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETED. OK TO CANCEL OR WITHDRAW CONTRACTOR OPEN NEW APP M00626007 ATOI PETER

OBJECTION FOR APPLICATION #: Z163297
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 002) DRINKING WATER FOUNTAIN NOT GFCI PROTECTED. ART.422.52
RSLV 05/22/2021 05/22/2021 11/16/2021
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 009) APT 908 MISSING PANEL COVER. ART.110.2
RSLV 05/22/2021 05/22/2021 11/16/2021
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 027) GFCI NOT PROVIDED FOR KITCHEN COUNTER ART.210.8
RSLV 05/22/2021 05/22/2021 11/16/2021
 
004 ( 26) ARMORED CABLES ARE INSTALLED EXPOSED
(FLOOR: 035) BX EXPOSE APT 35D ART. 320.15
RSLV 05/22/2021 05/22/2021 11/16/2021
 
005 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 036) APT 36B AFCI BREAKERS NOT WORKING ART.110.2
RSLV 05/22/2021 05/22/2021 11/16/2021
 
006 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(ALL FLOORS) CEILING TEMPORARY NOT REMOVED ART.590.3
RSLV 05/22/2021 05/22/2021 11/16/2021
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)FLOOR OUTLETS AND NID BOX OUTLETS NOT TR TYPE T-OUT ART.406.11
RSLV 05/22/2021 05/22/2021 11/16/2021
 
008 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) HALLWAY WOOD OUTLETS SET BACK ART.314.20
RSLV 05/22/2021 05/22/2021 11/16/2021
 
009 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)AC UNITS FROM 4 TO 25 FLOOR FUSED NOT AS PER MANUFACTURED SPEC.ART.110.2
RSLV 05/22/2021 05/22/2021 11/16/2021
 
010 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) BALCONY OUTLET NOT WR TYPE ART.406.8
RSLV 05/22/2021 05/22/2021 11/16/2021
 
011 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)ALL 30 AMP DRYER OUTLET NOT PROPERLY GROUNDED ART.250.122
RSLV 05/22/2021 05/22/2021 11/16/2021
 
012 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS) 25 D TO 35 D LINE KITCHEN GFCI NOT PROVIDED ART.210.8
RSLV 05/22/2021 05/22/2021 11/16/2021
 
013 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS)AFCI NOT PROVIDED FOR SMOKE AND SHADE OUTLETS T-OUT ART.210.12
RSLV 05/22/2021 05/22/2021 11/16/2021
 
014 (999) OTHER
(ALL FLOORS)AFFIDAVIT FOR ALL KITCHEN APPLIANCES NO ACCESS TO THE WIRING
RSLV 05/22/2021 05/22/2021 11/16/2021
 
015 (999) OTHER
(ALL FLOORS) ELEVATORS NOT INSPECTED.
RSLV 05/22/2021 05/22/2021 11/16/2021
 
016 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR) PANELS MISSING DIRECTORY ART 408.4
RSLV 05/22/2021 05/22/2021 11/16/2021