| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
288 |
273-2/0, 14-3/0, 1-250 |
| D. Over 250 MCM |
46 |
14-350, 4-3/0, 28-500 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
288 |
273-125A, 14-150A, 1-200A |
| C. 3 Phase Up to 225 AMPS |
14 |
12-200A, 2-175A |
| D. 3 Phase Over 225 AMPS |
10 |
7-800A, 3-400A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
7 |
3-30HP, 4-40HP |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 002) DRINKING WATER FOUNTAIN NOT GFCI PROTECTED. ART.422.52 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 002 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 009) APT 908 MISSING PANEL COVER. ART.110.2 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 003 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 027) GFCI NOT PROVIDED FOR KITCHEN COUNTER ART.210.8 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 004 |
( 26) |
ARMORED CABLES ARE INSTALLED EXPOSED (FLOOR: 035) BX EXPOSE APT 35D ART. 320.15 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 005 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 036) APT 36B AFCI BREAKERS NOT WORKING ART.110.2 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 006 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (ALL FLOORS) CEILING TEMPORARY NOT REMOVED ART.590.3 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 007 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)FLOOR OUTLETS AND NID BOX OUTLETS NOT TR TYPE T-OUT ART.406.11 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 008 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) HALLWAY WOOD OUTLETS SET BACK ART.314.20 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 009 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)AC UNITS FROM 4 TO 25 FLOOR FUSED NOT AS PER MANUFACTURED SPEC.ART.110.2 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 010 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) BALCONY OUTLET NOT WR TYPE ART.406.8 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 011 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS)ALL 30 AMP DRYER OUTLET NOT PROPERLY GROUNDED ART.250.122 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 012 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS) 25 D TO 35 D LINE KITCHEN GFCI NOT PROVIDED ART.210.8 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 013 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS)AFCI NOT PROVIDED FOR SMOKE AND SHADE OUTLETS T-OUT ART.210.12 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 014 |
(999) |
OTHER (ALL FLOORS)AFFIDAVIT FOR ALL KITCHEN APPLIANCES NO ACCESS TO THE WIRING |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 015 |
(999) |
OTHER (ALL FLOORS) ELEVATORS NOT INSPECTED. |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |
| |
| 016 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) PANELS MISSING DIRECTORY ART 408.4 |
RSLV |
05/22/2021 |
05/22/2021 |
11/16/2021 |