| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
125 AMP S.S |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
1 |
1- SET 1/0 WIRE |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
1-42 CKT PANEL |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (BASEMENT) FEEDER TAP OVER 25 FEET 240.21 |
RSLV |
12/05/2018 |
12/05/2018 |
02/05/2019 |
| |
| 002 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 007) 210.8, RECEPTACLE IN MEDICINE ARE NOT GFCI PROTECTED. |
RSLV |
12/24/2018 |
12/24/2018 |
02/05/2019 |
| |
| 003 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 007)210.12(B), AFCI BREAKER ARE NOT PROVIDE FOR BRANCH CIRCUIT. |
RSLV |
12/24/2018 |
12/24/2018 |
02/05/2019 |
| |
| 004 |
(999) |
OTHER (FLOOR: 007)314.20, JUNCTION BOXES SET WITH COMBUSTIBLE AND NON COMBUSTIBLE1/4", THRU-OUT. |
RSLV |
12/24/2018 |
12/24/2018 |
02/05/2019 |
| |
| 005 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (BASEMENT) 250.24(A)(5), NEUTRAL BOND AFTER SERVICE SWITCH. |
RSLV |
12/24/2018 |
12/24/2018 |
02/05/2019 |
| |
| 006 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 007) BX WITHOUT BOX 110.2A |
RSLV |
02/05/2019 |
02/05/2019 |
03/08/2019 |
| |
| 007 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 007) MISSING BX CONNECTORS HALLWAY OUTLETS 110.2A |
RSLV |
02/05/2019 |
02/05/2019 |
03/08/2019 |
| |
| 008 |
( 41) |
LOCKNUTS ARE NOT MADE UP TIGHT (BASEMENT) LOCKNUTS NOT TIGHT DISCONNECT SWITCH 300.11 |
RSLV |
02/05/2019 |
02/05/2019 |
03/08/2019 |
| |
| 009 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (BASEMENT) EMT PIPE NOT SUPPORTED 358.30 T-OUT |
RSLV |
02/05/2019 |
02/05/2019 |
03/08/2019 |
| |
| 010 |
(999) |
OTHER (BASEMENT)CONTRACTOR NEEDS TO AMEND APP REMOVE SERVICE SWITCH FROM APP |
RSLV |
02/05/2019 |
02/05/2019 |
03/08/2019 |
| |
| 011 |
(999) |
OTHER (BASEMENT) CONDUIT PENETRATION ARE NOT PROPERLY SEAL T-OUT 300.21 |
RSLV |
02/05/2019 |
02/05/2019 |
03/08/2019 |
| |
| 012 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 007) NEW PANEL |
RSLV |
03/08/2019 |
03/08/2019 |
04/09/2019 |
| |
| 013 |
(999) |
OTHER (FLOOR: 007) CONDUIT BODY COVER MUST REMAIN ACCESSIBLE 314.29 |
RSLV |
03/08/2019 |
03/08/2019 |
04/09/2019 |
| |
| 014 |
(999) |
OTHER (FLOOR: 007) NEW PANEL AFCI MISSING 210.12 |
RSLV |
03/08/2019 |
03/08/2019 |
04/09/2019 |
| |
| 015 |
(999) |
OTHER (FLOOR: 007) NEW PANEL NOT GROUNDED 250.112 |
RSLV |
03/08/2019 |
03/08/2019 |
04/09/2019 |
| |
| 016 |
(999) |
OTHER (BASEMENT) METER PAN NEUTRAL BOND 250.24 |
RSLV |
03/08/2019 |
03/08/2019 |
04/09/2019 |
| |
| 017 |
(999) |
OTHER (BASEMENT) DISC SW. NEUTRAL BROKEN 110.2 |
RSLV |
03/08/2019 |
03/08/2019 |
04/09/2019 |
| |
| 018 |
(999) |
OTHER (BASEMENT) TAP PARALLEL CONDUCTORS NOT IN SAME MANNER 310.4 |
OPEN |
03/08/2019 |
03/08/2019 |
|
| |
| 019 |
(999) |
OTHER (BASEMENT)BONDING BUSHING NEEDED FOR FITTING ENTERING LOOSE CONCENTRIC KO OFSWITCH 300.10 |
OPEN |
04/09/2019 |
04/09/2019 |
|