BIS Menu   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: Z163094
Premises: 546 ISHAM STREET MANHATTAN BIN: 1064851     Block: 2227   Lot: 11
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 546 ISHAM ST Census Tract:   293 Health Area:  0110
BASEMENT Admin Area:   Z - UPPER MANHATTAN Inspection Area:   A
NEW YORK, NY 10034 Community Board:   112
DOB Cross Street(s):   SHERMAN AVENUE,    VERMILYEA AVENUE
Status:   C - JOB IS SIGNED OFF 12/04/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/06/2017 4:45 PM
Application Entered:   10/06/2017 Job Start Date:   10/06/2017
Last Change:   12/04/2020 Job End Date:   12/31/2017
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     12/03/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012665 Licensee Name: SHANE R O'CONNOR
Firm: 004502 Firm Name: NTS ELECTRICAL, INC
Firm Phone: 718-429-3234  Firm Address: 37-31 58TH STREET, SUITE B-1 WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $63.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PAUL COSTANZA
Owner Business Name: CHARTER COMMUNICATION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1-30 AMP DISCONNECT
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  2-NO.2 AWG / 1-NO. 10 AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/06/2017 Notice: C - CALL TO OFFICE 11/01/2020
Power Issued: 10/06/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: Z163094
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/17/2018 05/18/2018 DNM N (26) (0) Y
INSPECTION COMMENTS: ELECTRICIAN DID NOT SHOW.
 
(2) 07/06/2018 07/06/2018 AYC V (35) (3)
INSPECTION COMMENTS: FAIL
 
(3) 09/14/2018 09/14/2018 CLC H Y (30) (0)
INSPECTION COMMENTS: ONE OBJECTION REMAIN
 
(4) 10/02/2018 10/02/2018 GYM V R (55) (3)
INSPECTION COMMENTS: NEW OBJECTION.
 
(5) 10/22/2020 10/22/2020 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-20-000025290
 
(6) 10/31/2020 11/01/2020 TUR G X (1) (0) Y
INSPECTION COMMENTS: THIS JOB CANNOT BE CANCELLED IT STILL HAS TWO OPEN SELF CERTIFIABLE OBJECTIONS IN ITS QUE . MUST COMPLETE SUBMISSION TO CLOSE AS AN INSPECTION
 
(7) 11/18/2020 11/19/2020 GYM G R (40) (0)
INSPECTION COMMENTS: JOB NEED TO CERTIFIED. COMPLETE
 
(8) 12/03/2020 12/04/2020 GYM C (55) (0) Y
INSPECTION COMMENTS: COMPLETE.

OBJECTION FOR APPLICATION #: Z163094
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) DOUBLE LUGGING IN THE SS. ART. 110.14(A)
RSLV 07/06/2018 07/06/2018 09/14/2018
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT)ADEQUATE CLEARANCE NOT PROVIDED IN FRONT OF THE SS. ART. 110.26
RSLV 07/06/2018 07/06/2018 10/02/2018
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) NEUTRAL BAR IS NOT BONDED. ART. 250.24
RSLV 07/06/2018 07/06/2018 09/14/2018
 
004 (999) OTHER
(BASEMENT) NO GROUNDING ELECTRODE CONDUCTOR PROVIDED 250.64
RSLV 10/02/2018 10/02/2018 11/18/2020
 
005 (999) OTHER
(BASEMENT) SERVICE NEUTRAL NOT BONDED 250.28
RSLV 10/02/2018 10/02/2018 11/18/2020
 
006 (999) OTHER
(BASEMENT) SERVICE ENTRANCE CONDUITS NOT BONDED 250.92
RSLV 10/02/2018 10/02/2018 10/22/2020